11.5. DISTRIBUTION BLOWER SPEED CONFIGURATION

It is possible to adjust the speed of the distribution blower for circulation mode, air conditioning and any other mode of
auxiliary heaters.
NOTE: When heating with wood, the fan distribution speeds are programmed in order to provide the best thermal
exchange and cannot be changed.
It is possible to adjust the blower speed in "CIRCULATION" mode at any time by going in the main menu under
"CONFIGURATION" and "BLOWER SPEED".
The blower speed adjustments for auxiliary heating are available only if the option was activated. The selected speed
in this menu will be the speeds used in the "CIRC", "COOL" and "HEAT" mode.
The adjustment of all controls must be done by a qualified technician. The controls settings and the blower speed must
conform to the recommendations of the CMMTQ.

11.5.1. DISTRIBUTION FAN SPEEDS

Your furnace is equipped with a 4-speed blower. Using the central processing unit, we have created 6 functional
speeds. Refer to the following table for the various speed configurations.
Functional Speed Corresponding data
*These results were measured at exit of plenum during laboratory tests. Results may vary depending of the
configuration and installation.

11.6. SYSTEM BALANCING

It is important to call upon a professional installer for the installation of the furnace and the ducting system
configuration. Certain check-ups must be performed and certain rules must be respected in order not to damage the
blower.
When all components are installed on the furnace and the ducting system is connected to the various rooms of the
house, you must balance the ducting system. In order to do so, start the distribution blower by going in the
''TROUBLESHOOT LINK'' menu on Page 5 and select speed #4.
36
1
Blower speed #1 using 98V
2
Blower speed #1 using 115V
3
Blower speed #2 using 98V
4
Blower speed #2 using 115V
5
Blower speed #3 using 115V
6
Blower speed #4 using 115V
CFM* Static pressure
600
0.2" H
O
2
760
0.2" H
O
2
840
0.2" H
O
2
950
0.2" H
O
2
1150
0.2" H
O
2
1260
0.2" H
O
2