Wall-Mounted Remote Control Wiring
WARNING
The wiring should adapt to the wire control current.
Otherwise, electric leakage or overheating may occur
and result in fire.
The specified cables shall be used in the wiring. No
external force may be applied to the terminal.
Otherwise, the wire may be damaged and heating may
occur and result in fire.
CAUTION
The shielded wire must be grounded.
The connecting cable should not be longer than 20m (65.5').
The remote control operates on a low voltage circuit
loops. DO NOT connect a 220V or 380V cable to the
circuit loop.
Make sure that configured tubes are 30-50cm (12-20")
or more apart.
DO NOT employ an ohmmeter to detect the insulation
after wiring the remote control.