Installation; Field Wiring Diagrams - Viking B-1 Technical Data Manual

Table of Contents

Advertisement

Deluge Devices 270d
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
5. Remote Annunciator (RZA-4X)
Mounts on standard single-gang box. (LED Interface Module (4XLM) described above is required).
Provides "System Trouble" LED
Local Piezo Sounder
Silence Switch (for local sounder)
Alarm/Waterfl ow Bell LED
Waterfl ow/Supervisory Bell LED
Releasing Circuit 1 LED
Supervisory Bell/Release Circuit 2 LED.
6. End-of-Line resistor
4.7K, ½ Watt, with terminal connector both ends, (for two-wire supervised circuits)
7. Power Supervisory Relay Coil
For four-wire smoke detector circuits
8. Voltage and Current Meters (4XZMM)
Mount inside cabinet
9. Digital Communicator NOTI-FIRE 911
Kit For Central Station service
10. RFI Retrofit Kit
Includes Ferrite Beads, Transzorb and Dead Front Protective Panel

4. INSTALLATION

Prior to installation, review the Par-3 Owner's Manual and Viking Field Wiring Diagrams. (See package inside panel.) Observe all
instructions provided in the Par-3 Owner's Manual. Field wiring must be according to VIKING FIELD WIRING DIAGRAMS for the
specifi c mode of operation required. See Table 1.
All wiring should be done in accordance with National and/or Local codes for fi re alarm systems.
The Authority Having Jurisdiction may have additional requirements.
1.
Mount the cabinet in a clean, dry, vibration-free area where temperature and humidity conditions do not exceed limitations indi-
cated in TECHNICAL DATA.
2.
Verify that all initiating devices (detectors), indicating appliances, and releasing devices are compatible with the Model B-1 Par-3
Release Control Panel. Contact the Viking distributor for a list of compatible devices. Also, refer to appropriate Fire Protection
Equipment Approval Guides.
3.
Wire all alarm initiating devices sequentially for proper supervision.
4.
Pull required conductors through the knockouts provided.
5.
Prior to connecting to the panel, verify continuity of all circuitry.
6.
Prior to connecting to the panel, check for, and correct any short circuits.
7.
Make electrical connections to control panel for the detection, supervisory, alarm, trouble, and release circuits, according to ap-
propriate VIKING FIELD WIRING DIAGRAMS for the system used and the Owner's Manual provided with the panel.
a.
Where indicated on VIKING FIELD WIRING DIAGRAMS, install the 4.7 K Ohm ½ Watt End-of-Line Resistor (provided in
panel) at the remote end of circuit. End-of-Line Resistors should NOT be installed across Release Circuits.
b.
On all un-used circuits, leave the 4.7 K Ohm ½ Watt End-of-Line Resistor (provided in panel) in place.
c.
Maintain polarity on alarm bell and trouble bell circuits. Do not energize the panel until all associated, modules, and intercon-
necting cables have been connected.
8.
Prior to energizing the panel:
a.
Verify that dip switches controlling panel operation are in the proper position for the system used. Refer to Table 2 and VIKING

FIELD WIRING DIAGRAMS.

b.
Verify that all modules are securely and properly positioned on their pins. If a module is loose, carefully align all pins and
press firmly into position.
9.
Connect non-energized AC power to the panel. Refer to Figure 2 and VIKING FIELD WIRING DIAGRAMS.
a.
Connect the wire providing in-coming voltage to the terminal marked "H".
b.
Connect the neutral wire to the terminal marked "N".
c.
Connect the ground wire to the terminal marked "G".
10.
Procedure for connecting Batteries: Note: Two battery plug/wire assemblies (long leads with plug) and jumper (short) wires are
provided with each panel. Connectors on one plug/wire assembly fit 7.0 AH Batteries. Connectors on the other plug/wire assembly
fit 12.0 AH Batteries.
a.
Position batteries end-to-end with terminals adjacent. Select the proper plug/wire assembly for the batteries used.
TECHNICAL DATA
(Viking P/N 07911)
(Viking Part No. 07913)
(Viking Part No. 07919)
(Viking Part No. 07917)
(Viking Part No. 07918)
(Viking Part No. 12696)
January 12, 2007
RELEASE CONTROL PANEL
MODEL B-1