Remote Annunciator Model Ra-4410Rc Operation; Basic Operation; Installation Instructions - Viking VFR-400 Manual

Hide thumbs Also See for VFR-400:
Table of Contents

Advertisement

REMOTE ANNUNCIATOR MODEL RA-4410RC OPERATION

Red LED's:
Initiating Device Circuits Active (4)
Notification/Release Circuits Active (4)
Pre-Discharge/Discharge
Common Alarm (1)
Green LED's:
Power On
Yellow LED's:
Initiating Device Circuits troubles (4)
Output Circuit Troubles (4)
Supervisory Initiating Zone (4)
Supervisory Bell Output Active (4)
(1) each: Supervisory 1, Supervisory 2, Power
Trouble, Supervisory/Abort Trouble, System Trouble,
Earth Fault, Signal Silenced

Basic Operation

The appropriate LED flashes to indicate a change of status on the panel. A trouble or supervisory condition will flash
the appropriate Yellow LED indicating the location of the condition. If any outputs are programmed as TROUBLE or
SUPERVISORY BELL, that Yellow output LED will flash indicating the output is activated. Pressing the TBL/SUP
ACKNOWLEDGE button on the panel changes the flashing zone Amber LED to steady on and turns the flashing Yellow output
LED off.
An alarm or low air alarm condition will flash a Red LED indicating the zone in alarm and any outputs mapped to that zone that
have activated. Pressing the SIGNAL SILENCE button changes the flashing Red Zone LED to steady on and the flashing Red
Output LED mapped to that zone off unless the output is programmed as RELEASE. In addition, the Yellow SIGNAL SILENCE
LED will light.
Any zone programmed as WATERFLOW is considered non-silenceable so the SIGNAL and TBL/SUP ACKNOWLEDGE
buttons will have no effect on the flashing zone and output LED's. A buzzer on the annunciator sounds for any trouble condition.
When the panel is in a normal state, pressing the LAMP TEST button can be used to test the LED's.
The release panel supervises and communicates with the annunciator via separate connections for the RS-485 communication and
24VDC power requirements of the RA-4410RC. Separate cables should be used for power and communication. Shielded cable
shall be used for the communication line. Up to three annunciators can be connected to one panel. A rotary switch is provided on
the panel to indicate how many annunciators are connected. Another rotary switch is on the annunciator to set the address. The
annunciators must be addressed consecutively. See page 20 for wiring information. Refer to bulletin #8840024 for installation
instructions and maximum wire run.

INSTALLATION INSTRUCTIONS

Read the entire manual before attempting to install this panel.
This panel wiring should be installed and maintained in accordance with section 760 (Fire Protection
Signaling Systems) and all other applicable sections of the National Electrical Code, all other applicable NFPA Code and
Standards, local code and the authority having jurisdiction. Review the circuit parameters listed below before installing the panel.
All wiring terminals support 14 to 22 AWG wire sizes. 18 AWG stranded or solid copper wire, (or wire size rated for the current
carrying capacity of the input and output circuit application), with 300V, 85°C insulation is recommended.
VFR-400 • 5403548 • REV W • 8/17
15
RA-4410RC
RED OUTPUT LED STEADY: ABORT
ZONE 1
ZONE 2
ZONE 3
ZONE 4
POWER ON
SUP 1/ABORT
POWER TBL
SUPERVISORY 2
SYSTEM TBL
COMMON ALARM
SUP /ABORT TBL
SIGNAL SILENCE
EARTH FAULT
STEADY: DISCHARGE
FLASHING: PRE-DISCHARGE
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
LAMP TEST
DWG# 3550-17