Viking B-1 Technical Data Manual page 6

Table of Contents

Advertisement

Deluge Devices 270f
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
CAUTION! SIMULTANEOUS OPERATION OF BOTH DETECTION CIRCUITS ON ANY SYSTEM UTILIZING CROSS-ZONE DETECTION
WILL RESULT IN OPERATION OF THE DELUGE VALVE. FAILURE TO CLOSE THE MAIN WATER SUPPLY CONTROL VALVE WILL
CAUSE WATER TO FLOW INTO THE SPRINKLER PIPING.
2.
Operate individual detectors, following instructions listed in technical data for the detector used. See Figure 2 for output circuits
and relays that should activate for the system used. "Detection" circuits are latching (except when configured for optional "timed
shut-off". See Owner's Manual).
3.
When Test is complete, push "System Reset". Conditions should return to normal.
4.
Refer to technical data for the system used to open main water supply control valve and place the system back in service.
II. Maintenance
CAUTION: DISCONNECT ALL POWER SOURCES BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAM-
AGED BY REMOVING AND/OR INSERTING CARDS, MODULES, OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER-
GIZED.
7. AVAILABILITY
The Viking Model B-1 Release Control Panel is available through a network of domestic and international distributors. See the Viking
Corp. Web site for closest distributor or contact The Viking Corporation.
8. GUARANTEES
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Name
Par-3
Par-3C
Par-3E
1
UL listed Releasing Device Control Unit (UOJZ)
2
cUL and CSA approved Par-3C
3
Accepted by New York City Department of Buildings (MEA 89-92-E) when confi gured for Single Hazard-Two
Zone operation (See Figure 1) and equipped with LED Interface Module (4XLM) and Remote Annuncitor
(RZA-4X) See ACCESSORIES
4
Listed by the California State Fire Marshall (7770-0533:105)
TECHNICAL DATA
Table 1 - Part Numbers and Approvals
Power Supply
110 VAC 50/60Hz
110 VAC 50/60Hz
220 VAC 50/60Hz
RELEASE CONTROL PANEL
Approvals
1
3
4
UL
, FM, NYC
and CSFM
2
cUL
FM
January 12, 2007
MODEL B-1
Viking Part
No.
07907
07953
07908

Advertisement

Table of Contents
loading

Table of Contents