January 12, 2007
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
N. Front Panel Control Switches
•
Switch 1: Tone Silence
•
Switch 2: Alarm Silence - Tone Silence and Alarm Silence control switches can be activated to acknowledge alarms. A second
"trouble" will resound the piezo.
•
Switch 3: Alarm Activate -The Alarm Activate switch may be used to activate indicating circuits and relays.
•
Switch 4: System Reset - The Reset switch clears any activated output circuits. If alarm or trouble conditions exist when the reset
switch is pushed, they will re-activate the panel.
O. Front Panel Zone Status LEDs
•
When the panel is activated, zone status LEDs illuminate, to indicate the status of Zone 1, Zone 2, Alarm Pressure, and Auxiliary
Supervisory circuits.
•
Alarm (red) LEDs indicate activation of a detection device.
•
Trouble (yellow) LEDs indicate electrical circuit failure, such as short circuits and loose wires.
P. Front Panel System Status LEDs
•
The presence of AC Power is indicated by a constant green LED, indicating normal conditions.
•
Alarm (red), Trouble (yellow), and Supervisory (yellow) LEDs activate as required to indicate System Alarm, Release operation,
Supervisory Device activation, and Circuit trouble.
•
LEDs also illuminate to indicate when the Alarm Silence switch has been activated.
Q. Last Event Recall
•
Follow procedure printed in Par-3 Owner's Manual provided with panel.
R. Zone Disable Function
•
Follow procedure printed in Par-3 Owner's Manual provided with panel.
S. Battery Fail and Earth Fault supervision
•
See Figure 2 for location of LEDs
T. Discharge timer option
•
Latched, 10 or 15 minutes. Refer to Par-3 Owner's manual included with panel. Also refer to installation standards, Technical
Data, and all Authorities Having Jurisdiction when using timer confi gurations.
•
Output circuits protected against false activation by two step command sequence
U. Slide in zone identification labels
•
Spare labels included in Par-3 Owner's Manual provided with panel.
V. Other Features
•
Piezo Sounder
•
Alarm signals are latching
•
Trouble signals are self restoring
•
Alarm and Trouble resound
II. Ordering Information
Part Numbers - Refer to Table 1
Available since 1991
A. Modules and Accessories
1. Batteries
•
Two batteries of the same AH rating are required.
•
12V 7 Amp-Hour Viking P/N 07920
•
12V 12 Amp-Hour Viking P/N 07921 12V 18 Amp-Hour Viking P/N 09867
•
Plug-in connector is provided with the Panel.
•
See POWER CALCULATIONS to determine which batteries meet standby battery requirements.
2. Zone Relay Module (4XZM)
•
Model B-1 Panels can accommodate a second 4XZM Zone Relay Module (one included in each panel) or one of the following
two Modules:
3. Transmitter Module (4XTM)
•
Provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity circuits.
4. LED Interface Module (4XLM)
•
For Remote Annunciator (RZA-4X) described below (Required for NYC approval).
TECHNICAL DATA
(Refer to Figure 1)
(order separately)
(Viking Part No. 07912)
(Viking P/N 07909)
(Viking P/N 07910)
Deluge Devices 270c
RELEASE CONTROL PANEL
MODEL B-1