Viking B-1 Technical Data Manual page 3

Table of Contents

Advertisement

January 12, 2007
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
N. Front Panel Control Switches
Switch 1: Tone Silence
Switch 2: Alarm Silence - Tone Silence and Alarm Silence control switches can be activated to acknowledge alarms. A second
"trouble" will resound the piezo.
Switch 3: Alarm Activate -The Alarm Activate switch may be used to activate indicating circuits and relays.
Switch 4: System Reset - The Reset switch clears any activated output circuits. If alarm or trouble conditions exist when the reset
switch is pushed, they will re-activate the panel.
O. Front Panel Zone Status LEDs
When the panel is activated, zone status LEDs illuminate, to indicate the status of Zone 1, Zone 2, Alarm Pressure, and Auxiliary
Supervisory circuits.
Alarm (red) LEDs indicate activation of a detection device.
Trouble (yellow) LEDs indicate electrical circuit failure, such as short circuits and loose wires.
P. Front Panel System Status LEDs
The presence of AC Power is indicated by a constant green LED, indicating normal conditions.
Alarm (red), Trouble (yellow), and Supervisory (yellow) LEDs activate as required to indicate System Alarm, Release operation,
Supervisory Device activation, and Circuit trouble.
LEDs also illuminate to indicate when the Alarm Silence switch has been activated.
Q. Last Event Recall
Follow procedure printed in Par-3 Owner's Manual provided with panel.
R. Zone Disable Function
Follow procedure printed in Par-3 Owner's Manual provided with panel.
S. Battery Fail and Earth Fault supervision
See Figure 2 for location of LEDs
T. Discharge timer option
Latched, 10 or 15 minutes. Refer to Par-3 Owner's manual included with panel. Also refer to installation standards, Technical
Data, and all Authorities Having Jurisdiction when using timer confi gurations.
Output circuits protected against false activation by two step command sequence
U. Slide in zone identification labels
Spare labels included in Par-3 Owner's Manual provided with panel.
V. Other Features
Piezo Sounder
Alarm signals are latching
Trouble signals are self restoring
Alarm and Trouble resound
II. Ordering Information
Part Numbers - Refer to Table 1
Available since 1991
A. Modules and Accessories
1. Batteries
Two batteries of the same AH rating are required.
12V 7 Amp-Hour Viking P/N 07920
12V 12 Amp-Hour Viking P/N 07921 12V 18 Amp-Hour Viking P/N 09867
Plug-in connector is provided with the Panel.
See POWER CALCULATIONS to determine which batteries meet standby battery requirements.
2. Zone Relay Module (4XZM)
Model B-1 Panels can accommodate a second 4XZM Zone Relay Module (one included in each panel) or one of the following
two Modules:
3. Transmitter Module (4XTM)
Provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity circuits.
4. LED Interface Module (4XLM)
For Remote Annunciator (RZA-4X) described below (Required for NYC approval).
TECHNICAL DATA
(Refer to Figure 1)
(order separately)
(Viking Part No. 07912)
(Viking P/N 07909)
(Viking P/N 07910)
Deluge Devices 270c
RELEASE CONTROL PANEL
MODEL B-1