Preparing for installation
Preparing for installation
■ Safety valve
■ Diaphragm expansion vessel
■ Plate heat exchanger for DHW heating
Connecting accessories
A time switch (accessories) can be con-
nected to the control unit with a low volt-
age supply.
Siting
Suitable siting locations include:
■ Recreational rooms and other living
spaces
■ Ancillary rooms without own ventila-
tion
Operation of the Vitodens 050-W in wet rooms
A r
The Vitodens is approved for installation
in wet rooms (e.g. bathroom or shower
rooms) (protection IP X4 D, splash-
proof).
8
(cont.)
e a
A r
e a
1
2
A r
e a
0
Area 2
■ Cupboards (open at the top)
■ Recesses without compulsory clear-
ance towards combustible materials
■ Attic rooms (pitched attics and long
panes) where the balanced flue can be
routed directly through the roof
Since the flue pipe connection for room-
sealed operation is surrounded by com-
bustion air (coaxial pipe), no clearances
towards combustible materials need be
maintained. For further details, see the
technical guide "Flue systems for the
Vitodens".
The installation area must be safe from
the risk of frost.
6 0
0
When installing the Vitodens in wet
areas, observe the safety zones and
minimum wall clearances according to
VDE 0100 [or local regulations] (see also
"Electrical safety zone"). The Vitodens
may be installed in area 1 if hosed water
(e.g. from massage showers) is preven-
ted.