Viessmann Vitodens 050-W Installation And Service Instructions Manual page 47

Wall mounted gas condensing boiler
Table of Contents

Advertisement

Fault display
(cont.)
Displayed
System characteris-
fault code
tics
52
Burner blocked
59
No DHW heating
5 A
Burner blocked
A9
Control mode without
OpenTherm influ-
ence
b0
Burner blocked
b8
Burner blocked
E3
Burner in a fault
state
E5
Burner blocked
F0
Burner blocked
F1
Burner in a fault
state
F2
Burner in a fault
state
Cause
Short circuit, flow
sensor
Lead break, outlet
temperature sen-
sor
Lead break, flow
sensor
Communication er-
ror, OpenTherm
device
Short circuit, flue
gas temperature
sensor
Lead break, flue
gas temperature
sensor
Fault in safety
chain
Internal fault
Internal fault
Max. flue gas tem-
perature exceeded
Temperature limit-
er has responded
Troubleshooting
Measures
Check connections and
lead; replace sensor if re-
quired.
Check sensor (see
page 54).
Check connections and
lead; replace sensor if re-
quired.
Check connections and
lead; replace OpenTherm
if required.
Check sensor (see
page 55).
Check sensor (see
page 55).
Check the temperature
limiter and connecting ca-
bles (see page 53).
Check the ionisation elec-
trode and connecting ca-
bles.
Replace control unit.
Check heating system fill
level. Check circulation
pump. Vent the system.
Check heating system fill
level. Check circulation
pump. Vent the system.
Check the temperature
limiter and connecting ca-
bles (see page 53).
Press "Reset" (see
page 49).
47