SPECIAL FUNCTION

11-1. ROTATION FUNCTION(AND BACK-UP FUNCTION, 2ND STAGE CUT-IN FUNCTION)
For PCA-RP50/60/71/100/125/140GA#1,PCA-RP50GA2#1
11-1-1. Operation
(1) Rotation function (and Back-up function)
• Outline of functions
· Main and sub unit operate alternately according to the interval of rotation setting.
w Main and sub unit should be set by refrigerant address.(Outdoor Dip switch setting)
Refrigerant address"00"
Refrigerant address"01"
· When error occurrs to one unit, another unit will start operation.(Back-up function)
• System constraint
· This function is available only by the grouping control system(INDOOR UNIT : OUTDOOR UNIT=1:1) of 2 refrigerant
groups.(Refer to Fig. 1)
· Main indoor unit should be connected for wired remote controller and the transmission line(TB5) for main and sub unit
should also be connected. (Refer to Fig. 1)
(This function cannot be set by wireless remote controller.)
· Set refrigerant address of each unit.(Dip switch on the outdoor unit···Refrigerant address 00/01)
Operation pattern
[Back-up function only]··· Request code number "312"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
[Rotation function] & [Back-up function]··· Request code number "313~318"
Start operation
Main
unit
IC-1
Sub
unit
IC-2
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Note:
· When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start
operation.
· To operate the main unit, refer to the 11-1-2. and set the requet code No. which is not the same as the current one, and set
again the former request code No.
(2) 2nd stage cut-in function
Outline of functions
· Number of operating units is determined according to the room temperature and set point.
· When room temperature becomes higher than set point, standby unit starts.(2 units operation)
· When room temperature falls below set point -4:, standby unit stops.(1 unit operation)
System constraint
· This function is available only in rota-
tion operation and back-up function in
cooling mode.
Downloaded from AC-Manual.com Manuals
Main unit
Sub unit
Error occurs on main unit.
Main
Run
Stop
Main
Sub
Sub
Run
Stop
Stop
Run
1~28 days
1~28 days
[2nd stage cut-in function]··· Request code number "322~324"
Main
unit
IC-1
Sub
unit
IC-2
Sub
Abnormal condition
Run
Error occurs on main unit.
Main
Main
Sub
Abnormal condition
Run
Stop
Run
Room temp.
Start operation
Sub unit start operation
Run
Stop
33
33
Fig. 1
Refrigerant address
"00"
OC-1
Main
3(2)
unit
IC-1
2
2
RC
OC : Outdoor unit
IC : Indoor unit
RC : Wired remote controller
Set point
Room temp. < Set point -4
Sub unit stop
Run
Stop
Refrigerant address
"01"
OC-2
Sub
3(2)
unit
IC-2