4. CONTROL SYSTEM
50
Scheduled operation setting
- Movement path :
The method of use is the same as
in "2) User setting".
Figure 31 Scheduled operation setting screen
Figure 32 Schedule setting example screen
* For setting method, please refer to "Example)".
Example)
① The Scheduled operation can be set in one of the 8 patterns. (Run/stop time, temperature and current value can be set)
② Pattern application can be classified by 5 types.
③ Select one of the "5 types" after choosing the date for the Scheduled operation in calendar.
▶ Description of an example for Scheduled application
① Aug 1, 2009: Run at 06:00 / Stop at 09:00, Run at 09:00 / Stop at 12:00
② Aug 9, 2009: Run at 06:00 / Stop at 09:00, Run at 09:00 / Stop at 12:00,
Run at 12:00 / Stop at 15:00, Run at 15:00 / Stop at 18:00
In each step, it is possible to set Operate time, Stop time, applicable weekdays and control temperature.
In User setting, make sure whether the present date and time have been correctly set.