Stop Running The Product - LG RCWW Operation & Maintenance Manual

Water-cooled screw chiller
Table of Contents

Advertisement

6-5. Stop running the product

• When stopping the product, perform it in the following order.
Press Stop button
Compressor stops.
Stopping is
completed
Figure 55 Stopping Procedure
1) When the Stop button in the control panel is pressed,
the slide valve will be closed automatically.
2) Items to check after stopping
- Stop the cooling water pump.
Close slowly the pump outlet valve before stopping
the pump.
- Stop the chilled water pump.
Close slowly the pump outlet valve before stopping
the pump.
- Record the levels of the refrigerant and oil after stop-
ping.
6. Commissioning
87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lcww

Table of Contents