Adjust Menu; Reload Factory Defaults - Slant/Fin SF-10 Operation And Instruction Manual

Boiler temperature control
Table of Contents

Advertisement

MODE 7 – External Direct Drive Operation
Adjust Menu (1 of 1)
Item Field

RELOAD FACTORY DEFAULTS

To reload FACTORY DEFAULT SETTINGS, press and hold the outside
buttons (Item and Down) while powering the control up. This will reload
the FACTORY DEFAULTS.
Access
Description
Factory
MODE
Installer
Select the operating mode for the control.
BOILER MAXIMUM
Factory
Select the maximum boiler water temperature.
PUMP DELAY
Factory
Select the boiler pump purge time after a shutting
off the burner.
TEMPERATURE UNITS
Factory
Select to display temperature in degrees Fahrenheit
Installer
or in degrees Celsius.
Range
1, 2, 3, 4, 5, 6, 7
Default = 3
120 to 225°F, OFF
(49 to 107°C, OFF)
Default = 180°F (82°C)
OFF, 0:20 to 9:55 min,
On
Default = 0:20 min
°F, °C
Default = °F
Model SF-10 Control Instructions Manual
Settings
29