Slant/Fin SF-10 Operation And Instruction Manual page 23

Boiler temperature control
Table of Contents

Advertisement

MODE 3 and 4 – Outdoor Reset & DHW Operation
Adjust Menu (2 of 2)
Item Field
Access
Description
STAGE DELAY
Factory
Select the minimum time delay between stages.
Installer
Note: This setting is not used in this application.
DIFFERENTIAL
Factory
Select the differential that the control is to use
when it is operating the boiler.
DHW BOILER TARGET
Factory
Select the boiler target temperature while heating
an indirect DHW tank.
DHW MODE
Select no priority (1) or priority (2) of indirect DHW
heating over space heating.
Factory
Note: This item is only available when MODE is
set to 3.
PUMP DELAY
Factory
Select the boiler pump purge time after shutting
off the burner.
WARM WEATHER SHUT DOWN
Factory
Select the space heating system's warm weather
Installer
shut down when using outdoor reset.
TEMPERATURE UNITS
Factory
Select to display temperature in degrees Fahrenheit
Installer
or in degrees Celsius.
Range
Au, 0:30 to 9:55 min
Default = Au
Au, 2 to 42°F
(Au, 1 to 23°C)
Default = Au
OFF, 70 to 220°F
(OFF, 21 to 104°C)
Default = 180°F (82°C)
1, 2
Default = 1
OFF, 0:20 to 9:55 min,
On
Default = 0:20 min
35 to 100°F, OFF
(2 to 38°C, OFF)
Default = 65°F (18°C)
°F, °C
Default = °F
Model SF-10 Control Instructions Manual