Control (Dip Switch) Settings - Slant/Fin SF-10 Operation And Instruction Manual

Boiler temperature control
Table of Contents

Advertisement

TESTING THE CONTROL'S OUTPUTS
The control has a built-in test routine that is used to override the main control functions. The test sequence is enabled
when the Up button is pressed and held for 5 seconds while in the View menu. The test sequence can be cancelled by press-
ing either the Item, Up or Down button. Once the test sequence is enabled, the outputs are tested in the following sequence:
Press and hold the up button for 3 seconds while in the View menu.
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
The control exits the test sequence and resumes normal operation.
Control Settings
DIP SWITCH SETTING
Note: DIP switches are located on the front of the control. Remove bottom cover and screw for access.
(1) Factory / Installer
The Factory / Installer DIP switch is used to select which items are available to
be viewed and / or adjusted in the user interface. The Factory Access Level
includes all the settings available in the control. The Installer Access Level
includes the settings and items which are required for system setup.
(2) Not Used
16
Model SF-10 Control Instructions Manual
The boiler pump is turned on.
Stage 1 burner is turned on.
Stage 2 burner is turned on. Note: Stage 2 is not used in this application.
The boiler pump, Stage 1 and Stage 2 are shut off. The DHW pump is
turned on for 10 seconds.
The DHW pump shuts off. The alarm contact is closed for 10 seconds
2
OFF
1
OFF
Factory
Installer