Server IP
Set up the IP address of a PLC in the Modbus TCP
Client mode
Server Port
Set up the server port of a PLC in the Modbus TCP
Client mode
Response Timeout
Modbus TCP Client
Set up the timeout timer from 50ms to 100000ms.
If the set value is out of range, it will be
automatically changed to its maximum or minimum
value. The default is 300ms.
Scan Interval
Set up the time for scan interval, ranging from
20ms to 60000ms; the default is 3000ms.
Read/Write
Set up the access permissions for the mapped
register address; the default is read-only.
Slave ID
Set up the corresponding slave communication
port. The value is between 1 and 255.
Slave Starting Address
Set up the slave starting address (decimal) for
read/write the registers in a PLC.
Device Starting Address
Set up the device starting address (decimal, starting
from 2048).
If the mapped address is with "Read" permission,
Add Mappings
data read from appointed registers in the PLC will
be stored in this device starting address. If the
mapped register address is with "Write"
permission, data from the device starting address
will be stored in the appointed registers in the PLC.
Length (1-123)
Here displays the number of the continuous
address followed by the default mapped address.
Operation
Delete the selected mapped address.
Add Mappings
Click the button to add mappings; up to 100
addresses can be set up.
Description
C ha pt er 3 I ntr o duc t i on t o F u nc t i o ns
Default
N/A
502
300
30000
Read
N/A
N/A
N/A
N/A
N/A
N/A
_3
3 - 2 9