Stop Bits
Set up the stop bits for the serial port. Options are 1
and 2.
Parity Bits
Set up the parity bits for the serial port. Options are
None, Odd and Even.
MODBUS ID
Set up the MODBUS ID. The value is between 1 and 255.
MODBUS Mode
Set up the communication mode for the device.
MODBUS Timeout
Set up the timeout timer from 200ms to 5000ms. If the set value is out of range,
it will be automatically changed to its maximum or minimum value.
Scan Interval
Set up the time for scan interval, ranging from 20ms
to 60000ms.
Read/Write
Set up the access permissions for the mapped
register address; the default is read-only.
Slave ID
Set up the corresponding slave communication
port. The value is between 1 and 255.
Slave Starting Address (decimal)
Master Mode
Set up the slave starting address (decimal) for
read/write the registers in a PLC.
Device Starting Address (decimal)
Set up the device starting address (decimal, starting
from 2048).
If the mapped address is with "Read" permission,
data read from appointed registers in the PLC will
be stored in this device starting address. If the
mapped register address is with "Write" permission,
data from the device starting address will be stored
in the appointed registers in the PLC.
Length (1-123)
Here displays the number of the continuous
Description
Transparent mode: 7, 8
Modbus RTU: 8
C ha pt er 3 I ntr o duc t i on t o F u nc t i o ns
Default
1
None
1
MODBUS RTU
200ms
30000ms
Read
N/A
N/A
N/A
N/A
_3
3 - 2 7