Allen-Bradley 1609-P3000N Quick Start Manual page 7

Hide thumbs Also See for 1609-P3000N:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
U
C
SER
ONFIGURABLE
F
UNCTION
Automatic Self-Test
UPS ID
Date of Last Battery
Replacement
Minimum Capacity Before
Return from Shutdown
Alarm Delay After
Line Failure
Shutdown Delay
Duration of
Low Battery Warning
Synchronized Turn-on Delay
High Bypass Point
Low Bypass Point
Output Voltage
Output Frequency
Number of
Battery Packs
I
TEMS
N
: S
OTE
ETTINGS ARE MADE THROUGH SUPPLIED
N
M
OPTIONAL
ETWORK
F
ACTORY
D
EFAULT
Every 14 days
Every 7 days(168 hours),
(336 hours)
14 days (336 hours)
On Startup Only,
No Self-Test
UPS_IDEN
Up to eight characters to define the UPS
Manufacture Date
Date of
Battery Replacement mm/dd/yy
0 percent
0, 15, 25, 35, 50, 60, 75,
90 percent
5 second delay
5 or 30 second delay
At Low Battery
Never
20 seconds
0, 20, 60, 120, 240, 480,
720, 960 seconds
2, 5, 7, 10, 12, 15, 18, 20 minutes
2 minutes
PowerChute software
provides automatic,
unattended shutdown
when approximately
2 minutes of battery
operated runtime remains.
0 seconds
0, 20, 60, 120, 240, 480,
720, 960 seconds
+10% of output
+5%, +10%, +15%, +20%
voltage setting
-30% of output
-15%, -20%, -25%, -30%
voltage setting
3 kVA 120 V models:
3 kVA 120 V models:
120 VAC
120 VAC
208/230 V models:
208/230 V models:
230 VAC
200, 208, 220, 230, 240 VAC
Automatic
50 ± 3 Hz
50 ± 0.1 Hz
50 ± 3 Hz or
60 ± 3 Hz
60 ± 3 Hz
60 ± 0.1 Hz
1
Number of Connected Internal Battery
Packs, (two modules per pack)
6
P
C
OWER
,
T
ANAGEMENT CARDS
OR
ERMINAL
U
S
C
SER
ELECTABLE
HOICES
,
HUTE SOFTWARE
M
.
ODE
D
ESCRIPTION
Set the interval at which the UPS will execute a
self-test.
Uniquely identify the UPS, (i.e. server name or
location) for network management purposes.
Reset this date when you replace the battery
modules.
Following a low-battery shutdown, the battery
modules will be charged to the specified
percentage before powering connected
equipment.
Mute ongoing alarms or disable all alarms
permanently.
Set the interval between the time when the UPS
receives a shutdown command and the actual
shutdown.
The low battery warning beeps are continuous
when two minutes of run time remain.
Change the warning interval default to a higher
setting if the operating system requires a longer
interval for shutdown.
The UPS will wait the specified time after the
return of utility power before turn-on (to avoid
branch circuit overload).
Maximum voltage that the UPS will pass to
connected equipment during internal bypass
operation.
Minimum voltage that the UPS will pass to
connected equipment during internal bypass
operation.
Allows the user to select the UPS output voltage
while online.
Sets the allowable UPS output frequency.
Whenever possible, the output frequency tracks
the input frequency.
Defines the number of connected battery packs
for proper run time prediction.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1609-p3000h1609-p3000a1609-p5000e

Table of Contents