GAMEWELL SMARTNET SYSTEM

OVERVIEW:

SmartNet System

INSTALLATION AND WIRING

MSTR-422 Module

MSTR-FIB Module

SIM-422 Module

SIM-422/FIB Module

Technical Manuals Online! - http://www.tech-man.com
The Gamewell SmartNet system is a Personal Computer based proprietary fire
alarm control system. It is designed to monitor and control up to 250 Flex 600
panels. The SmartNet system consists of either a SN600-PC15, SN600-PC19 or a
SN600-PC19R Computer with a network interface module installed. The central
controller features point and click operation with all programming and control
functions performed from one location. Network status windows indicate the status
of all connected panels. Each panels history is recorded and saved in its own
individual file.
The network interface module, part number MSTR-422 is a module that plugs into
the SN600-PCxx bus expansion slot. This card provides an RS-422 communication
medium for the Gamewell Smartnet network. The network card is factory installed
into the second expansion slot. It provides two plug in terminal block connectors at
the rear of the computer console. The right terminal block (JP2) is factory set to
COM 4, Addr 02E8, IRQ7 and the left block (JP1) is set to COM 3, Addr 03E8,
IRQ5 (see appendix A for settings). The SmartNet network wiring terminates to the
connector JP1 (out) which is the Primary Bus and JP2 (return) which is the
Secondary Bus. Refer to installation drawing A-M1095 in appendix B. Four LED's
are provided to indicate the status of the communications (See A-M1095 in
appendix B for details).
The MSTR-FIB modules provides the same features as the MSTR-422 with the
exception of the connections to the network. The MSTR-FIB module connects to the
network nodes via two fiber optic cables. The fiber optic connection will allow a
node to be located up to 1.2 miles (2Km) apart Transit/`receive left side is the
primary connection and the transmit/ receive right is the secondary bus.
s Note: Do not connect or disconnect the
ribbon cable when power is applied to the
panel.
s Note: Refer to drawing D-W1164
The SIM-422 module mounts on the bus driver card of the IF600 system (node),
providing a hard wired connection to the network. It is connected to the CPU 's
ISBX0 connector with a 34 pin ribbon cable that supplies power and data. An eight
position DIP switch is used to set node addresses. Set the appropriate binary
switches to the open position to select an address for the node. Two LED's are
provided to indicate communication. LED1 indicates Network communication and
LED2 indicates Node communication.
The SIM-422/FIB Module provides the same features as the SIM-422 module with
exception to the hard wired connection to the to the JP2 port. JP2 is removed and
replaced with a fiber optic connection R1 and T1. These designate transmit and
receive connections for the fiber optic cables.