Password window

CONTROLS

General

Control Buttons

Acknowledging

Signal Silence

Technical Manuals Online! - http://www.tech-man.com
The password window will appear when the user is trying to perform a control
function. The password characters will appear as asterisks in the password window
when entered. The passwords are a combination of numbers and letters from three to
ten characters long. A separate maintenance program under the service menu is used
to program passwords.
The default passwords are as follows:
ONE
TWO
THREE
FOUR
FIVE
SIX
GAMEWELL
To perform any functions on a network node, click the mouse on that unit's number
in the node window. If the node is in the normal condition clicking the mouse on
the node number will allow direct communication to the node selected to perform
monitoring, programming, and history recall functions. When a unit is selected the
network data window will have a blue background. The title block for the network
display window will change from "network data" to "node # data". The number for
the selected unit will have a black bar through it. The data window will show the
last message received from that node. Click on another unit's number to redirect
communication , or the current unit's number to go back to the network data mode.
Control buttons are only present when the unit is selected and the associated action
can be taken.
Acknowledge: Acknowledges alarms and troubles and silences the panel audible.
Reset: Resets alarm and trouble conditions.
Signal Silence: Turns on and off the local indicating circuits (toggle function).
Delete: Deletes messages from the status window one at a time
Confirm: Confirms that a message was received.
When an alarm or trouble condition is received, the user will be prompted with an
acknowledge button. When the user clicks the mouse on the acknowledge button the
password window will appear above the data window (See Figure 1). The user must
then enter the correct password, which shows up as asterisks, and hit the enter key
on the keypad. The console will emit a short steady-tone audible indicating the
correct password and the condition will be acknowledged. The user will then be
prompted with a reset button. (Certain troubles such as class A need to be reset.) For
an alarm condition a signal silence button will be available with an additional
password needed. If the user enters the incorrect password, the user will have to
click the button again to activate the password window.
The Signal silence button is used to toggle the active indicating circuits,
programmed to silence when this function is used. Use of this button requires
password access. The circuits that have been silenced will be displayed in the
"Silenced Nodes" status window.