Resetting

Multiple Alarms and/or
Troubles

Confirming

Deleting

Scroll control

Trouble

Alarm

Technical Manuals Online! - http://www.tech-man.com
When an alarm or trouble condition is acknowledged, the user will be prompted with
a reset button. When the user clicks the mouse on the reset button, a reset password
window will appear above the data window. The user must then enter the correct
password and hit the enter key on the keypad. The console will emit a short steady
tone audible indicating the correct password, the condition will be reset, and the title
above the associated status window will change from red to black. (Certain troubles
such as class A faults also need to be reset.) If the user enters the incorrect
password, the user will have to click the reset button again to activate the password
window.
Every alarm, supervisory or trouble must be acknowledged and confirmed before the
console silences. If an alarm condition(s) exists when a trouble condition is received,
the trouble will be displayed in the status. All alarms will be displayed in the alarm
status display box, all troubles will be displayed in the trouble status display box and
all supervisory alarms will be displayed in the supervisory alarm status display box.
When a condition is displayed in a status window the related audible will sound and
the confirm button will be visible. Select the desired item with the mouse and click
on the confirm button. A confirmed item will have an asterisk at the right side of the
confirmed events. All events must be confirmed. [Password required]
When a condition shown in a status window has been corrected or eliminated the
item in the window will be marked with an arrow on the left side. and the delete
button will be visible. use the mouse button to select the item in the window, then
click on the delete button. [Password required]
Allows user to scroll through data, status data, in a specific windows. Place the
mouse on the arrows to advance one line at a time in the desired direction. Place the
mouse on the upper or lower half of the scroll bar to advance one message block at a
time.
If the network is in a normal condition and a trouble condition is received from a
node, the SmartNet console will sound a slow intermittent audible, the network data
window will go into the direct access mode for the node displaying the trouble
message from the console, the trouble status window will display the trouble
condition with the title in red, and the user will be prompted with an acknowledge
button.
If the network is in a normal condition and an alarm condition is received from a
node, the SmartNet console will sound a three pulse coded audible, the network data
window will go into the direct access mode displaying the alarm message from the
node, the alarm status window will display the alarm condition and the user will be
prompted with an acknowledge button.
Audible Indications
CONDITION
Code 3, Temporal
Alarm
Trouble
.5 sec on, 3.5 sec off, repeat
Supervisory
.5 sec on, .5 sec off, .5 sec on, 2.5 sec off, repeat
.5 sec on, 6.5 sec off, repeat
Delete
Watchdog
Steady
Table 1
AUDIBLE TONE
6