Privileges

Configuring the
Communication
Technical Manuals Online! - http://www.tech-man.com
The file PRIV.INI assigns the various access levels to the SmartNet functions. There
are six access levels of passwords that can be assigned. The following is the default
access levels assigned to the various functions.
RESET = 3
ACK = 3
PRINTER = 2
SILENCE = 3
COMM = 2
BUS = 2
EXIT = 6
DELETE = 3
CONFIRM = 3
MAINT = 5
CommLogParm=COM2:9600,n,8,1,RS,CS0,CD0,DS0 (this line is present only
when the serial data output is used.)
HEARTBEAT=YES/NO (Heartbeat refers to the supervision of the computers serial
port. When YES is used the system will output NODE 0 SYSTEM NORMAL every
2 minutes). If NO is selected the heartbeat information is not transmitted.
Assigning various levels of access to these functions can be accomplished by
changing the associated number.
The COMM.INI file allows the configuration of the SmartNet communications
ports. The default configuration is as follows:
nbs10cards = 2
nbs10io1 = &H3E8
nbs10irq1 = 5
nbs10freq = 18.432
nbs10io2 = &H2E8
nbs10irq2 = 7
nbs10freq2 = 18.432
baudRate = 19200
maxRetries = 0
timeout1 = 150
timeout2 = 300
The "nbs10cards = " statement defines Class A or Class B wiring. 1 = Class B, 2 =
Class A. All other entries in this file should not be changed.
8