8.4.3 Heating Mode
8.4.3.1 Compressor running rules:
The maximum operation frequency of the compressor after starting submits to the following rule.
If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to outdoor ambient temp. During the 7 minutes, the frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
34
33
28
27
25
24
22
21
19
18
17
16
15
14
12
11
6
5
Off
Fmax=F2
Fmax=F3
Fmax=F4
Fmax=F5
Fmax=F6
Fmax=F7
Fmax=F8
Fmax=F9
Fmax=F10
35