Electrical Specifications - Daikin FXAQ-MAVE Technical Data Manual

Wall mounted unit
Table of Contents

Advertisement

1
Specifications

1-2 ELECTRICAL SPECIFICATIONS

Power Supply
Name
Phase
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps (MFA) A
Full load amps (FLA)
Voltage range
Minimum
Maximum
Notes
• Indoor Units • WALL MOUNTED UNIT • FXAQ-MAVE
FXAQ20MAVE
FXAQ25MAVE
1
Hz
50
V
A
0.30
15.00
A
0.20
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
Maximum allowable voltage range variation between phases is 2%.
For more details concerning conditional connections, see http://extranet.daikineurope.com, select "E-Data Books".
®
• VRV
Systems • Indoor Units
FXAQ32MAVE
FXAQ40MAVE
VE
1
1
50
50
220-240
0.40
0.40
15.00
15.00
0.30
0.30
-10%
+10%
or above listed range limits.
MCA/MFA : MCA = 1.25 x FLA
MFA<= 4 x FLA
next lower standard fuse rating minimum 15A
select wire size based on the MCA
instead of a fuse, use a circuit breaker