9.2 Diagnosis and Solution
9.2.1 Over current protection occurs 4 times diagnosis and solution
Check if the voltage of the
power supply is too low ?
No
Is the outdoor
operation temperature
too high? Does the
outdoor unit has bad
air circulation?
No
Check if the outdoor
fan can run properly?
Yes
Disconnect with the power
and replace the main PCB.
Turn on the units and check
if the problem remains
Yes
Repair the power supply.
Yes
Correct the operation condition.
Correct the connection of fan
No
motor or replace the fan motor.
Check if the compressor
Yes
is normal running
Replace the capillary.
Evacuate the system
and recharge refrigerant.
No
Yes
Replace the
compressor