Error Codes Table - Panasonic WH-ADC0916G9E8 WH-UX09FE8 Service Manual

Hide thumbs Also See for WH-ADC0916G9E8 WH-UX09FE8:
Table of Contents

Advertisement

17.4

Error Codes Table

Diagnosis display
Abnormality/Protection control
H00
No abnormality detected
H12
Indoor/Outdoor capacity unmatched
Outdoor compressor temperature sensor
H15
abnormality
H20
Water pump abnormality
Indoor refrigerant liquid temperature
H23
sensor abnormality
H27
Service valve error
H42
Compressor low pressure abnormality
H62
Water flow switch abnormality
*H63
Refrigerant low pressure abnormality
H64
Refrigerant high pressure abnormality
*H65
Deice circulation error
H70
Back-up heater OLP abnormality
H72
Tank sensor abnormal
Indoor - control panel communication
H76
abnormality
H90
Indoor/outdoor abnormal communication
H91
Tank heater OLP abnormality
H95
Indoor/Outdoor wrong connection
Outdoor high pressure overload
H98
protection
H99
Indoor heat exchanger freeze prevention
F12
Pressure switch activate
F14
Outdoor compressor abnormal revolution
F15
Outdoor fan motor lock abnormality
F16
Total running current protection
Outdoor compressor overheating
F20
protection
IPM (power transistor) overheating
F22
protection
Outdoor Direct Current (DC) peak
F23
detection
F24
Refrigeration cycle abnormality
Cooling/Heating cycle changeover
F25
abnormality
F27
Pressure switch abnormality
Abnormality judgement
90s after power supply
Continue for 5 sec.
Continue for 10 sec.
Continue for 5 sec.
Continue for 5 minutes
Continue for 1 min.
Continue for 5 sec.
Continue for 5 sec.
Continue for 10 sec.
Continue for 60 sec.
Continue for 5 sec.
> 1 min after starting operation
Continue for 60 sec.
4 times occurrence within
20 minutes
4 times occurrence within
20 minutes
2 times occurrence within
30 minutes
3 times occurrence within
20 minutes
4 times occurrence within
30 minutes
3 times occurrence within
30 minutes
7 times occurrence
continuously
2 times occurrence within
20 minutes
4 times occurrence within
30 minutes
Continue for 1 min.
107
Primary location to verify
 Indoor/outdoor connection wire
 Indoor/outdoor PCB
 Specification and combination table in
catalogue
 Compressor temperature sensor
(defective or disconnected)
 Indoor PCB
 Water pump (malfunction)
 Refrigerant liquid temperature sensor
(defective or disconnected)
 High pressure sensor (defective or
disconnected)
 Outdoor pipe temperature sensor
 Clogged expansion valve or strainer
 Insufficient refrigerant
 Outdoor PCB
 Compressor
 Water flow switch
 Outdoor low pressure sensor
(defective or disconnected)
 Outdoor high pressure sensor
(defective or disconnected)
 Water flow switch sensor (defective or
disconnected)
 Water pump malfunction
 Buffer tank (is used)
 Back-up heater OLP
(Disconnection or activated)
 Tank sensor
 Indoor - control panel
(defective or disconnected)
 Internal/external cable connections
 Indoor/Outdoor PCB
 Tank heater OLP
(Disconnection or activated)
 Indoor/Outdoor supply voltage
 Outdoor high pressure sensor
 Water pump or water leakage
 Clogged expansion valve or strainer
 Excess refrigerant
 Outdoor PCB
 Indoor heat exchanger
 Refrigerant shortage
 Pressure switch
 Outdoor compressor
 Outdoor PCB
 Outdoor fan motor
 Excess refrigerant
 Outdoor PCB
 Compressor tank temperature sensor
 Clogged expansion valve or strainer
 Insufficient refrigerant
 Outdoor PCB
 Compressor
 Improper heat exchange
 IPM (Power transistor)
 Outdoor PCB
 Compressor
 Insufficient refrigerant
 Outdoor PCB
 Compressor low compression
 4-way valve
 V-coil
 Pressure switch