15.3 Error Codes Table
Diagnosis
Abnormality /
display
Protection control
H00
No memory of failure
Indoor/outdoor
H11
abnormal
communication
Indoor unit capacity
H12
unmatched
Indoor intake air
H14
temperature sensor
abnormality
Compressor
H15
temperature sensor
abnormality
Outdoor current
H16
transformer (CT)
abnormality
Indoor fan motor
H19
mechanism lock
Indoor float switch
H21
operation abnormal
Indoor heat
exchanger
H23
temperature sensor
abnormality
Indoor heat
exchanger
H24
temperature sensor
2 abnormality
Outdoor air
H27
temperature sensor
abnormality
Outdoor heat
exchanger
H28
temperature sensor
1 abnormality
Outdoor discharge
H30
pipe temperature
sensor abnormality
Indoor / outdoor
H33
misconnection
abnormality
Indoor drain water
H35
adverse current
abnormal
Indoor/Outdoor
H38
mismatch (brand
code)
Outdoor fan motor
H97
mechanism lock
Indoor high pressure
H98
protection
Indoor operating unit
H99
freeze protection
4-way valve
F11
switching
abnormality
Power factor
correction
F90
(PFC) circuit
protection
Refrigeration cycle
F91
abnormality
Compressor
F93
abnormal revolution
Abnormality
Protection
Judgment
Operation
—
Normal operation
Indoor fan only
operation can
After operation for
start by entering
1 minute
into force cooling
operation
90s after power
supply
Continuous for 5s
Continuous for 5s
—
Continuous
happen for 7 times
—
Continuous for 5s
Continuous for 5s
Continuous for 5s
Continuous for 5s
Continuous for 5s
—
—
—
2 times happen
within 30 minutes
—
—
4 times happen
within 30 minutes
4 times happen
within 10 minutes
2 times happen
within 20 minutes
4 times happen
within 20 minutes
Problem
—
Indoor/outdoor
communication not
establish
Total indoor capability
more than maximum limit
—
or less than minimum limit,
or number of indoor unit
less than two
Indoor intake air
—
temperature sensor open
or short circuit
Compressor temperature
—
sensor open or short circuit
Current transformer faulty
—
or compressor faulty
Indoor fan motor lock or
—
feedback abnormal
—
—
Indoor heat exchanger
—
temperature sensor open
or short circuit
Indoor heat exchanger
—
temperature sensor 2 open
or short circuit
Outdoor air temperature
—
sensor open or short circuit
Outdoor heat exchanger
—
temperature sensor 1 open
or short circuit
Outdoor discharge pipe
—
temperature sensor open
or short circuit
Indoor and outdoor rated
—
voltage different
—
—
—
Brand code not match
Outdoor fan motor lock or
—
feedback abnormal
Indoor high pressure
—
protection (Heating)
Indoor freeze protection
—
(Cooling)
4-way valve switching
—
abnormal
Power factor correction
—
circuit abnormal
Refrigeration cycle
—
abnormal
Compressor abnormal
—
revolution
58
Check location
—
Indoor/outdoor wire terminal
Indoor/outdoor PCB
Indoor/outdoor connection wire
Indoor/outdoor connection wire
Indoor/outdoor PCB
Specification and combination
table in catalogue
Indoor intake air temperature
sensor lead wire and connector
Compressor temperature
sensor lead wire and connector
Outdoor PCB faulty or
compressor faulty
Fan motor lead wire and
connector
Fan motor lock or block
—
Indoor heat exchanger
temperature sensor lead wire
and connector
Indoor heat exchanger
temperature sensor 2 lead wire
and connector
Outdoor air temperature sensor
lead wire and connector
Outdoor heat exchanger
temperature sensor 1 lead wire
and connector
Outdoor discharge pipe
temperature sensor lead wire
and connector
Indoor and outdoor units check
—
Check indoor unit and outdoor
unit
Outdoor fan motor lead wire
and connector
Fan motor lock or block
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
4-way valve
Lead wire and connector
Outdoor PCB faulty
Insufficient refrigerant or valve
close
Power transistor module faulty
or compressor lock