Daikin FXFQ20 P9VEB Technical Data Manual page 25

Hide thumbs Also See for FXFQ20 P9VEB:
Table of Contents

Advertisement

10
Air flow patterns
9 - 2 Sound Pressure Spectrum
FXFQ50P9
Approximate
threshold hearing
for continuous
noise
Octave band center frequency (Hz)
NOTES
Over All (dB):
(B, G, N is already rectified)
Operating conditons:
Power source: 220~240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Power level (dB):
Hi 51
Measuring place: Anechoic chamber
Location of microphone
Drain up
Mic. position
Note: Operation noise differs with operation and ambient conditions.
FXFQ80P9
Approximate
threshold hearing
for continuous
noise
Octave band center frequency (Hz)
NOTES
Over All (dB):
(B, G, N is already rectified)
Operating conditons:
Power source: 220~240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Power level (dB):
Hi 55
Measuring place: Anechoic chamber
Location of microphone
Drain up
Mic. position
Note: Operation noise differs with operation and ambient conditions.
• Indoor Unit • Round flow cassette • FXFQ-P9
Hi
Low
4D056871
Mode
Scale
Hi
Low
A
33.0
28.0
C
39.0
34.0
Hi
Low
4D056873
Mode
Scale
Hi
Low
A
38.0
32.0
C
44.0
38.0
®
• VRV
Systems • Indoor Unit
FXFQ63P9
Low
(Heating)
Low
Approximate
(cooling)
threshold hearing
for continuous
noise
Octave band center frequency (Hz)
Scale
Over All (dB):
Cooling Heating Cooling
(B, G, N is already rectified)
A
34.0
C
40.0
Operating conditons:
Power source: 220-240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Power level (dB):
Measuring place: Anechoic chamber
Location of microphone
Drain up
Mic. position
Note: Operation noise differs with operation and ambient conditions.
FXFQ100P9
Low
(cooling)
Approximate
threshold hearing
for continuous
noise
Octave band center frequency (Hz)
Scale
Over All (dB):
Cooling Heating Cooling Heating
(B, G, N is already rectified)
A
41.0
C
47.0
Operating conditons:
Power source: 220~240V 50Hz/220V 60Hz
Cooling: return air temperature: 27°C DB, 19°C WB - outdoor temperature: 35°C DB, 24°C WB
Heating: return air temperature: 20°C DB, 15°C WB - outdoor temperature: 7°C DB, 6°C WB
4 direction discharge
Power level (dB):
Measuring place: Anechoic chamber
Location of microphone
Drain up
Mic. position
Note: Operation noise differs with operation and ambient conditions.
Hi
(Heating)
Hi
(cooling)
4D056872
Mode
Hi
Low
Heating
36.0
29.0
30.0
42.0
35.0
36.0
Hi
Cooling Heating
52
54
Hi
(cooling)
Hi
(Heating)
Low
(Heating)
4D056874
Mode
Hi
Low
42.0
33.0
34.0
48.0
39.0
40.0
Hi
Cooling Heating
58
59
23

Hide quick links: