5
Dimensional drawings
5 - 1 Dimensional Drawings
FXFQ125P9
Piping side
Drain side
View A
Hanging bolt
NOTE
1
Location of the nameplates - Unit body: on the control box - Decoration panel: on the panel frame at the motor side under the corner cover
2
When installing an optional accessory, refer to the installation drawings
For the fresh air intake kit an inspection port is necessary
3
In case of using a wireles remote control, this position will be a signal receiver. Refer to the drawing of the wireless remote control for more detail.
4
Make sure the spacing between the ceiling and the cassette is no more than 35mm. Max cailing opening: 910mm.
5
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air is inducted into the ceiling, an additionalinsulation is required (polyethylene foam,
thickness 10mm or more).
FXFQ125P9VEB
Piping side
Drain side
VIEW A
Hanging bolt
NOTES
1.
Location of the nameplates:
Unit body: on the control box.
Decoration panel: on the panel frame at the motor side under the
corner cover
2.
When installing an optional accessory, refer to the installation drawings.
For the fresh air intake kit an inspection part is necessary
3.
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. Max. ceiling opening: 910mm
4.
When the conditions exceed 30°C and RH 80% in de ceiling or fresh
air is included into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
• Indoor Unit • Round flow cassette • FXFQ-P9
(Ceiling opening)
300 or less
(Suspension position)
see note 3
see note 4
860~910 (Ceiling opening)
710 (Suspension position)
300 or less
See note 3
5.
Installation direction
Piping
®
• VRV
Systems • Indoor Unit
see note 4
Please respect the distances as shown on figure below
see note 4
See note 3
6.
Please respect the distances as shown on fi gure below
(*1) Does not count for build in light
(*2) Space needed to enter with vacuum-cleaner tube.
(*3) Keep the exhaust of decoration panel free.
See note 3
200mm or
more (*4)
1500mm or
more (*4)
Dust
opening
Piping
(*4) In case a discharge opening is closed with the 'sealing member' option,
Suction
grill
Item
Name
Remark
1
Liquid pipe connection
ø9.52 (Flare connection)
2
Gas pipe connection
ø15.90 (Flare connection)
3
Drain pipe connection
VP25 (ODø32, IDø25)
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
ODø32, IDø25
10
Knock out hole
View B
External
Other unit
Ventilator
surface
light
1500 or more
2000 or more
4000 or more
1500 mm
or more (*)
200 mm
or more
1500 mm
1500 mm
or more (*)
or more (*)
200 mm
1500 mm
or more
or more (*)
(*) In case a discharge opening is closed with
the "sealing member" option, the distance of
1500 mm can be reduced to 500 mm on the
closed side.
3TW28914-1C
Nr
Name
Description
1
Liquid pipe connection
Ø9.52 fl are connection
2
Gas pipe connection
Ø15.90 fl are connection
3
Drain pipe connection
VP25 (O.D.Ø32, I.D. Ø25)
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
O.D.Ø32, I.D. Ø26
10 Knock out hole
VIEW B
Ventilator
Other unit
External
surface
light (*1)
256
1500 or more
2000 or more
4000 or more
1500mm or
more (*4)
1500mm or
more (*4)
200mm or
more (*4)
1500mm or
more (*4)
the distance of 1500mm can be reduced to 500 mm on the closed side.