5
Dimensional drawings
5 - 1 Dimensional Drawings
FXFQ20,25,32,40,50,63P9
950
Piping side
Drain side
VIEW A
840
55
340
280
330
Hanging bolt
4 x M8~M10
NOTES
1
Location of the nameplates
- Unit body: on the control box cover.
- Decoration panel: on the panel frame at the motor side under the corner cover
2
When installing an optional accessory, refer to the installation drawings.
- For the fresh air intake kit an inspection port is necessary
3
In case of using an infrared remote control, this position will be a signal
receiver. Refer to the drawing of the infrared remote control for more detail.
FXFQ20-63P9VEB
Piping side
Drain side
VIEW A
Hanging bolt
NOTES
1.
Location of the nameplates:
•
Unit body: on the control box.
•
Decoration panel: on the panel frame at the motor side under the
corner cover
2.
When installing an optional accessory, refer to the installation drawings.
•
For the fresh air intake kit an inspection part is necessary
3.
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. Max. ceiling opening: 910mm
4.
When the conditions exceed 30°C and RH 80% in de ceiling or fresh
air is included into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
• Indoor Unit • Round flow cassette • FXFQ-P9
860-910 (Ceiling opening)
300 or less
710 (Suspension position
420
see note 3
420
55
55
840
35
4
SEE NOTE
4
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. MAX ceiling opening: 910mm.
5
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air
is inducted into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
6
Please respect the distances as shown on the figure
860~910 (Ceiling opening)
710 (Suspension position)
300 or less
See note 3
5.
Installation direction
Piping
®
• VRV
Systems • Indoor Unit
Nr
4
SEE NOTE
1
Liquid pipe connection
2
Gas pipe connection
3
Drain pipe connection
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
10
Knock out hole
SEE NOTE
55
35
4
SEE NOTE
See note 3
Model
FCQ35
FCQ50-60, FXFQ20~50
FCQ71, FXFQ63
6.
See note 3
1500mm or
more (*4)
Dust
opening
Piping
Suction
grill
Name
Description
ø A flare connection
ø B flare connection
VP25 (O.D. ø 32 /I.D. ø 25)
O.D. ø 32 /I.D. ø 26
MODEL
213
FXFQ20-50P9
FXFQ63P9
VIEW B
VENTILATOR
OTHER UNIT
EXTERNAL
6
SURFACE
LIGHT
1500 or more
2000 or more
4000 or more
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
(*) In case a discharge opening is closed with the 'sealing member' option,
the distance of 1500mm can be reduced to 500mm on the closed side.
3TW28834-1B
Nr
Name
Description
1
Liquid pipe connection
ØA fl are connection
2
Gas pipe connection
ØB fl are connection
3
Drain pipe connection
VP25 (O.D.Ø32, I.D. Ø25)
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
O.D.Ø32, I.D. Ø26
10 Knock out hole
A
B
6.35
9.52
6.35
12.7
9.52
15.9
VIEW B
Please respect the distances as shown on fi gure below
Ventilator
Other unit
External
surface
light (*1)
256
1500 or more
2000 or more
4000 or more
(*1) Does not count for build in light
(*2) Space needed to enter with vacuum-cleaner tube.
(*3) Keep the exhaust of decoration panel free.
1500mm or
more (*4)
200mm or
more (*4)
1500mm or
more (*4)
200mm or
more (*4)
1500mm or
more (*4)
(*4) In case a discharge opening is closed with the 'sealing member' option,
the distance of 1500mm can be reduced to 500 mm on the closed side.
3TW32464-1
A
B
6.35
12.7
9.52
15.9
11