Dimensional drawings

5 - 1 Dimensional Drawings
FXFQ20,25,32,40,50,63P9
950
Piping side
Drain side
VIEW A
840
55
340
280
330
Hanging bolt
4 x M8~M10
NOTES
1
Location of the nameplates
- Unit body: on the control box cover.
- Decoration panel: on the panel frame at the motor side under the corner cover
2
When installing an optional accessory, refer to the installation drawings.
- For the fresh air intake kit an inspection port is necessary
3
In case of using an infrared remote control, this position will be a signal
receiver. Refer to the drawing of the infrared remote control for more detail.
FXFQ20-63P9VEB
Piping side
Drain side
VIEW A
Hanging bolt
NOTES
1.
Location of the nameplates:
Unit body: on the control box.
Decoration panel: on the panel frame at the motor side under the
corner cover
2.
When installing an optional accessory, refer to the installation drawings.
For the fresh air intake kit an inspection part is necessary
3.
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. Max. ceiling opening: 910mm
4.
When the conditions exceed 30°C and RH 80% in de ceiling or fresh
air is included into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
• Indoor Unit • Round flow cassette • FXFQ-P9
860-910 (Ceiling opening)
300 or less
710 (Suspension position
420
see note 3
420
55
55
840
35
4
SEE NOTE
4
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. MAX ceiling opening: 910mm.
5
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air
is inducted into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
6
Please respect the distances as shown on the figure
860~910 (Ceiling opening)
710 (Suspension position)
300 or less
See note 3
5.
Installation direction
Piping
®
• VRV
Systems • Indoor Unit
Nr
4
SEE NOTE
1
Liquid pipe connection
2
Gas pipe connection
3
Drain pipe connection
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
10
Knock out hole
SEE NOTE
55
35
4
SEE NOTE
See note 3
Model
FCQ35
FCQ50-60, FXFQ20~50
FCQ71, FXFQ63
6.
See note 3
1500mm or
more (*4)
Dust
opening
Piping
Suction
grill
Name
Description
ø A flare connection
ø B flare connection
VP25 (O.D. ø 32 /I.D. ø 25)
O.D. ø 32 /I.D. ø 26
MODEL
213
FXFQ20-50P9
FXFQ63P9
VIEW B
VENTILATOR
OTHER UNIT
EXTERNAL
6
SURFACE
LIGHT
1500 or more
2000 or more
4000 or more
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
(*) In case a discharge opening is closed with the 'sealing member' option,
the distance of 1500mm can be reduced to 500mm on the closed side.
3TW28834-1B
Nr
Name
Description
1
Liquid pipe connection
ØA fl are connection
2
Gas pipe connection
ØB fl are connection
3
Drain pipe connection
VP25 (O.D.Ø32, I.D. Ø25)
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
O.D.Ø32, I.D. Ø26
10 Knock out hole
A
B
6.35
9.52
6.35
12.7
9.52
15.9
VIEW B
Please respect the distances as shown on fi gure below
Ventilator
Other unit
External
surface
light (*1)
256
1500 or more
2000 or more
4000 or more
(*1) Does not count for build in light
(*2) Space needed to enter with vacuum-cleaner tube.
(*3) Keep the exhaust of decoration panel free.
1500mm or
more (*4)
200mm or
more (*4)
1500mm or
more (*4)
200mm or
more (*4)
1500mm or
more (*4)
(*4) In case a discharge opening is closed with the 'sealing member' option,
the distance of 1500mm can be reduced to 500 mm on the closed side.
3TW32464-1
A
B
6.35
12.7
9.52
15.9
11