Appendix A Specifications; Maximum Ambient Operating Temperature; Emx2-111 Feature Rj-45 Port Pinouts - Raritan EMX2-888 User Manual

Hide thumbs Also See for EMX2-888:
Table of Contents

Advertisement

Appendix A Specifications

Maximum Ambient Operating Temperature

EMX2-111 Feature RJ-45 Port Pinouts

In This Chapter
Maximum Ambient Operating Temperature ..........................................440
EMX2-111 Feature RJ-45 Port Pinouts.................................................440
EMX2-888 Feature RJ-45 Port Pinouts.................................................441
Sensor RJ-12 Port Pinouts ....................................................................441
Serial RS-232 Port Pinouts....................................................................441
RS-485 Port Pinouts..............................................................................442
The maximum ambient operating temperature (TMA) for the EMX is the
same for all models regardless of the certification standard (CE or UL).
Specification
Max Ambient Temperature
RJ-45 Pin/signal definition
Pin No.
Signal
Direction
1
DTR
Output
2
GND
3
+5V
4
TxD
Output
5
RxD
Input
6
N/C
N/C
7
GND
8
DCD
Input
Measure
60 degrees Celsius
Description
Reserved
Signal Ground
Power for CIM
(200mA, fuse protected)
Warning: Pin 3 is only
intended for use with
Raritan devices.
Transmit Data (Data out)
Receive Data (Data in)
No Connection
Signal Ground
Reserved
440