Ratings And Capacity - Dunkirk PSB-3D Installation, Operation & Maintenance Manual

Plymouth steam series 2 gas-fired steam boilers
Table of Contents

Advertisement

BOILER MODEL
NUMBER
Intermittent
Ignition w/Vent
Damper
PSB-3D
(1)
PSB-4D
(1)
PSB-5D
(1)
PSB-6D
(1)
PSB-7D
(1)
PSB-8D
(1)
PSB-9D
(1)
* MBH = 1,000 Btuh. Btuh = British Thermal Unit Per Hour.
† For altitudes above 2,000 ft. reduce input rate 4% for each 1,000 ft. above sea level.
Heating Capacity is based on DOE (Department of Energy) test procedure.
Add model number suffix 'P' for Propane Gas.
(1)
Net AHRI steam Ratings shown are based on a piping and pickup allowance of 1.333.
Base selection of boiler size on "Net AHRI Rating" being equal to or greater than installed radiation in square feet.
Consult manufacturer before selecting a boiler for installations having unusual piping and pickup requirements,such as
intermittent system operation, exhaust piping systems, etc.

RATINGS AND CAPACITY

Table 1 - Ratings and Capacities
No. of
Sec.
Fuel Type
Natural Gas
3
Propane
Natural Gas
4
Propane
Natural Gas
5
Propane
Natural Gas
6
Propane
Natural Gas
7
Propane
Natural Gas
8
Propane
Natural Gas
9
Propane
Heating
Input
Capacity
AFUE(%)
*MBTUH
*MBTUH
75
62
70
58
112
91
105
85
150
122
140
114
187
153
175
143
225
183
210
171
262
214
245
200
299
245
280
229
3
†Natural Gas
Net AHRI
Rating *Mbh
82.7
47
82.7
44
82.0
68
80.4
64
82.0
92
80.6
86
82.0
115
80.9
107
82.0
137
81.1
128
82.0
161
81.3
150
82.0
184
81.5
172
P/N 14683003, Rev. D [08/03/2015]