Daikin RZQG-L(8)Y1 Technical Data Manual page 20

Pair, twin, triple, double twin
Hide thumbs Also See for RZQG-L(8)Y1:
Table of Contents

Advertisement

6
Capacity tables
6 - 1 Cooling/Heating Capacity Tables
RZQG125L9V1
RZQG125L8Y1
Cooling
6
Cooling capacity [kW]
Cooling
25
Indoor
TC
SHC
WB
DB
kW
kW
16,0
22
14,10
9,54
18,0
25
14,70
9,50
19,0
27
15,00
9,52
19,5
27
15,21
9,52
22,0
30
16,00
9,39
24,0
32
16,70
9,31
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2.
= Maximum at standard conditions
= Rated capacity and rated coefficient of the power input
The maximum capacity is not guaranteed except at standard conditions.
3. SHC is based on indoor units EWB & EDB.
SHC for other dry bulb temperatures = SHC + SHC*
SHC* = SHC correction for other dry bulb temperatures
= 0.02 x AFR (m³/min) x (1 BF) x (DB* EDB)
4. The capacities are based on the following conditions:
Outdoor air: 85% RH
However, the outdoor ambient condition of the rated capacity during heating operation is 7°C DB / 6°C WB.
Corresponding refrigerant piping length: 5.0 m
Level difference: 0m
5. CPI is a percentage value compared to the rated value which is 1.00.
6. The error rate for this value is less than 5% and depends on the indoor unit type.
7. The heating performance takes into account the drop that occurs during defrost operation.
8. The air flow rate and bypass factor are mentioned in the table.
Pair
FCQHG125F
FCQG125F
AFR
33.5
33.0
(BF)
(0.19)
(0.21)
Twin
FCQG60F X 2
FBQ60C X 2
AFR
13.6 x 2
18 x 2
(BF)
(0.2 x 2)
(0.15 x 2)
Triple
FCQG50F X 3
FBQ50C X 3
AFR
12.6 x 3
16 x3
(BF)
(0.22 x 3)
(0.16 x 3)
Double twin
FCQG35F X 4
FBQ35C X 4
AFR
12.5 x 4
16 x4
(BF)
(0.4 x 4)
(0.15 x 4)
RZQG140L9V1
RZQG140LY1
Cooling
Cooling capacity [kW]
Cooling
25
Indoor
TC
SHC
WB
DB
kW
kW
16,0
22
15,50
10,47
18,0
25
16,17
10,55
19,0
27
16,56
10,43
19,5
27
16,74
10,49
22,0
30
17,61
10,37
24,0
32
18,38
10,20
Notes
1. The ratings shown are net capacities which include a deduction for indoor fan motor heat.
2.
= Maximum at standard conditions
= Rated capacity and rated coefficient of the power input
The maximum capacity is not guaranteed except at standard conditions.
3. SHC is based on indoor units EWB & EDB.
SHC for other dry bulb temperatures = SHC + SHC*
SHC* = SHC correction for other dry bulb temperatures
= 0.02 x AFR (m³/min) x (1 BF) x (DB* EDB)
4. The capacities are based on the following conditions:
Outdoor air: 85% RH
However, the outdoor ambient condition of the rated capacity during heating operation is 7°C DB / 6°C WB.
Corresponding refrigerant piping length: 5.0 m
Level difference: 0m
5. CPI is a percentage value compared to the rated value which is 1.00.
6. The error rate for this value is less than 5% and depends on the indoor unit type.
7. The heating performance takes into account the drop that occurs during defrost operation.
8. The air flow rate and bypass factor are mentioned in the table.
Pair
FCQHG140F
FCQG140F
AFR
33.5
33.0
(BF)
(0.15)
(0.23)
Twin
FCQHG71F X 2 FCQG71F X 2
AFR
21.2 x 2
21.5 x 2
(BF)
(0.2 x2)
(0.14 x 2)
Triple
FCQG50F X 3
FBQ50C X 3
AFR
12.6 x 3
16 x3
(BF)
(0.22 x 3)
(0.16 x 3)
Double twin
FCQG35F X 4
FBQ35C X 4
AFR
12.5 x 4
16 x4
(BF)
(0.4 x 4)
(0.15 x 4)
18
• Outdoor Unit • RZQG-L(8)Y1
Capacity range
Rated point
Outdoor temperature [°C DB]
30
35
CPI
TC
SHC
CPI
TC
SHC
CPI
kW
kW
kW
kW
1,00
13,60
9,30
1,10
13,10
9,12
1,20
1,00
14,20
9,32
1,10
13,70
9,09
1,21
14,00
9,06
1,21
1,01
14,50
9,34
1,11
1,01
14,68
9,26
1,12
14,15
9,08
1,21
1,01
15,47
9,14
1,12
14,90
8,95
1,23
1,02
16,10
9,09
1,13
15,50
8,83
1,24
FBQ125C
FHQG125C
FDQ125C
FVQ125C
FHQ125CA
FUQ125C
FBQ125D
39.0
31.0
39.0
28.0
31.0
32.5
34.0
(0.16)
(0.134)
(0.16)
(0.16)
(0.14)
(0.19)
(0.06)
FHQ60CA X 2
FFQ60C X 2
FDXS60F X 2
FBQ60D X 2
FNQ60A X 2
19.5 x 2
14.5 x 2
16 x 2
18 x 2
16 x 2
(0.20 x 2)
(0.11 x 2)
(0.12 x 2)
(0.18 x 2)
(0.12 x 2)
FHQ50CA X 3
FFQ50C X 3
FDXS50F9 X 3 FBQ50D X 3
FNQ50A X 3
15 x 3
12 x 3
16 x 3
15 x 3
16 x 3
(0.18 x 3)
(0.16 x 3)
(0.11 x 3)
(0.13 x 3)
(0.11 x 3)
FHQ35CA X 4
FFQ35C X 4
FDXS35F X 4
FBQ35D X 4
FNQ35A X 4
14 x 4
10 x 4
8.7 x 4
15 x 4
8.7 x 4
(0.17 x 4)
(0.25 x 4)
(0.17 x 4)
(0.08 x 4)
(0.17 x 4)
Capacity range
Rated point
Outdoor temperature [°C DB]
30
35
CPI
TC
SHC
CPI
TC
SHC
CPI
kW
kW
kW
kW
0,98
14,93
10,25
1,08
14,44
10,03
1,18
0,98
15,62
10,21
1,09
15,11
10,01
1,19
15,40
9,98
1,19
0,99
15,96
10,18
1,09
0,99
16,14
10,16
1,10
15,57
10,00
1,19
0,99
17,01
10,16
1,10
16,36
9,83
1,21
1,00
17,72
10,00
1,11
17,04
9,67
1,22
FBQ140C
FHQG140C
FVQ140C
FHQ140CA
FBQ140D
39:C/41:H
34.0
30.0
34.0
34.0
(0.14)
(0.17)
(0.18)
(0.17)
(0.06)
FBQ71C X 2
FHQG71C X 2
FAQ71C X 2
FHQ71CA X 2
FUQ71C X 2
FBQ71D X 2
18.0 x 2
20.5 x 2
18.0 x 2
20.5 x 2
23.0 x 2
18.0 x 2
(0.08 x 2)
(0.13 x 2)
(0.16 x 2)
(0.13 x 2)
(0.24 x2 )
(0.13 x2 )
FHQ50CA X 3
FFQ50C X 3
FDXS50F9 X 3 FBQ50D X 3
FNQ50A X 3
15 x 3
12 x 3
16 x 3
15 x 3
16 x 3
(0.18 x 3)
(0.16 x 3)
(0.11 x 3)
(0.13 x 3)
(0.11 x 3)
FHQ35CA X 4
FFQ35C X 4
FDXS35F X 4
FBQ35D X 4
FNQ35A X 4
14 x 4
10 x 4
8.7 x 4
15 x 4
8.7 x 4
(0.20 x 4)
(0.25 x 4)
(0.17 x 4)
(0.08 x 4)
(0.17 x 4)
• Split - Sky Air • RZQG-L(8)Y1
Heating
Capacity range
Heating capacity [kW]
Rated point
40
46
TC
SHC
CPI
TC
SHC
CPI
kW
kW
kW
kW
12,60
8,78
1,31
9,80
6,95
0,91
13,20
8,83
1,32
10,27
6,97
0,92
13,50
8,87
1,32
10,50
6,99
0,92
13,64
8,81
1,32
10,58
6,96
0,92
14,38
8,74
1,33
11,20
6,88
0,93
14,97
8,63
1,34
11,66
6,79
0,94
9. The rated power input for each model is mentioned in the table below.
Pair
FCQHG125F
FCQG125F
FBQ125C
FHQG125C
Cooling
3,00
3,22
3,15
3,58
Heating
3,07
3,72
3,53
3,48
Twin
FCQG60F X 2
FBQ60C X 2
FHQ60CA X 2
FFQ60C X 2
Cooling
3,14
3,28
3,67
3,61
Heating
3,64
3,74
4,11
4,10
Triple
FCQG50F X 3
FBQ50C X 3
FHQ50CA X 3
FFQ50C X 3
Cooling
3,17
3,28
3,66
3,23
Heating
3,66
3,74
4,10
3,55
Double twin
FCQG35F X 4
FBQ35C X 4
FHQ35CA X 4
FFQ35C X 4
Cooling
3,23
3,28
3,64
3,01
Heating
3,72
3,74
4,00
3,30
Heating
Capacity range
Heating capacity [kW]
Rated point
40
46
TC
SHC
CPI
TC
SHC
CPI
kW
kW
kW
kW
13,86
9,69
1,28
11,27
8,02
0,92
14,52
9,71
1,30
11,76
7,95
0,93
14,83
9,76
1,30
12,00
8,03
0,93
14,98
9,66
1,30
12,16
7,93
0,93
15,76
9,60
1,31
12,81
7,91
0,94
16,43
9,47
1,32
13,30
7,74
0,95
9. The rated power input for each model is mentioned in the table below.
Pair
FCQHG140F
FCQG140F
FBQ140C
FHQG140C
Cooling
4,00
4,17
4,02
4,05
Heating
3,77
4,30
4,30
4,27
Twin
FCQHG71F X 2 FCQG71F X 2
FBQ71C X 2
FHQG71C X 2
Cooling
3,94
4,11
3,75
3,59
Heating
3,71
4,24
4,70
4,47
Triple
FCQG50F X 3
FBQ50C X 3
FHQ50CA X 3
FFQ50C X 3
Cooling
4,12
3,75
4,25
4,15
Heating
4,24
4,70
5,43
4,15
Double twin
FCQG35F X 4
FBQ35C X 4
FHQ35CA X 4
FFQ35C X 4
Cooling
4,18
3,75
4,23
3,83
Heating
4,30
4,70
5,33
3,81
Symbols
AFR: Air flow rate [m³/min]
BF: Bypass factor
EWB: Entering wet bulb temperature (°C WB)
EDB: Entering dry bulb temperature (°C DB)
TC: Maximum total cooling/heating capacity [kW]
SHC: Sensible heat capacity [kW]
CPI: Coefficient of the power input
PI: Power input [kW]
compressor + indoor and outdoor fan motors
Heating
Outdoor temperature [°C WB]
FDQ125C
FVQ125C
FHQ125CA
FUQ125C
FBQ125D
3,20
3,74
3,58
3,44
3,63
3,53
3,65
3,48
3,86
3,46
FDXS60F X 2
FBQ60D X 2
FNQ60A X 2
3,75
4,10
3,75
4,20
3,85
4,20
FDXS50F9 X 3 FBQ50D X 3
FNQ50A X 3
3,45
3,97
3,45
3,61
3,81
3,61
FDXS35F X 4
FBQ35D X 4
FNQ35A X 4
3,94
3,74
3,94
4,45
3,78
4,45
Symbols
AFR: Air flow rate [m³/min]
BF: Bypass factor
EWB: Entering wet bulb temperature (°C WB)
EDB: Entering dry bulb temperature (°C DB)
TC: Maximum total cooling/heating capacity [kW]
SHC: Sensible heat capacity [kW]
CPI: Coefficient of the power input
PI: Power input [kW]
compressor + indoor and outdoor fan motors
Heating
Outdoor temperature [°C WB]
FVQ140C
FHQ140CA
FBQ140D
4,17
4,05
4,00
4,30
4,27
4,31
FAQ71C X 2
FHQ71CA X 2
FUQ71C X 2
FBQ71D X 2
3,81
3,59
3,35
3,75
4,68
4,47
4,36
4,70
FDXS50F9 X 3 FBQ50D X 3
FNQ50A X 3
4,26
3,75
4,26
4,37
4,70
4,37
FDXS35F X 4
FBQ35D X 4
FNQ35A X 4
5,38
3,75
5,38
5,85
4,70
5,85
3D076750F