Condensate connection
A Supply from the boiler
B Neutralising system or active char-
coal filter
C Drain to the drainage system
Connections on the heating water side
Flow and return
A Filling connection
18
Connect the condensate drain by the
shortest route, with a constant fall and a
pipe vent to the drainage system. Install
a neutralising system if required.
Note
■ ATV-DVWK-A 251 permits boiler use
without a neutralising system when
operating with low sulphur fuel oil
DIN 51605-EL-1 (sulphur content
≤ 50 mg/kg).
■ Use an active charcoal filter (acces-
sory) if not using a neutralising system.