10. Installation Instruction

10.1 Select the Best Location

10.1.1 Indoor Unit
There should not be any heat source or steam near
the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
Recommended installation height for indoor unit shall
be at least 2.5m.
10.1.2 Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
There should not be any animal or plant which could
be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
Do not place any obstacles which may cause a short
circuit of the discharged air.
If piping length is over the rated length, additional
refrigerant should be added as shown in the table
below:
Piping size
Model
Gas Liquid
9.52
6.35
YE9MKE
(3/8")
(1/4")
9.52
6.35
YE12MKE
(3/8")
(1/4")
12.7
6.35
YE18MKE
(1/2")
(1/4")
Example: If the unit is installed at a 10m distance, the
quantity
of additional refrigerant should be 50 g.
...... (10-7.5) m x 20g/m = 50 g
Min
Rated
Max
Piping
Piping
Length
Elevatio
Length
Length
(m)
n (m)
(m)
7.5
5
3
7.5
5
3
7.5
5
3
11.1.3 Indoor/Outdoor Unit
Max
Additional
Refrigeran
t (g/m)
(m)
15
20
15
20
15
20
*This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
20