10 Installation Instruction

10.1. CS-E15EKEA

10.1.1. Select The Best Location
INDOOR UNIT
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air circula-
tion.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over 7.5 m, additional refrigerant should be
added as shown in the table.
Piping size
Rated
Model
Length
Gas
Liquid
(m)
E15EK
1/2"
1/4"
7.5
Max
Max. piping
Additional
Elevation
Length
Refrigerant
(m)
(m)
(g/m)
5
15
20
10.1.2. Indoor/Outdoor
Diagram
27