Quiet Operation (Cooling Mode/Cooling Area Of Soft Dry Mode) - Panasonic CS-E15EKEA Service Manual

Hide thumbs Also See for CS-E15EKEA:
Table of Contents

Advertisement

1. Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated
above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1
below. When the air conditioner is stopped using remote control, the vane will shift to close position.
2. Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions
of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close
position.
Horizontal Airflow
1. Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the angles as
stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as
Figure 1 below.
Heating, with heat exchanger temperature
Cooling, Soft Dry and Ion
2. Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated below and the
positions of the vane are as Figure 2 above.
Pattern
Airflow Direction
Patterns at Remote
Control
Vane Angle (°)

11.3. Quiet operation (Cooling Mode/Cooling area of Soft Dry Mode)

A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
• When "quiet" button at remote control is pressed.
Quiet LED illuminates.
b. Quiet operation stop condition
Operation Mode
1
2
90
68
40
Vane Angle (°)
A
68 ~ 112
B
90
68 ~ 112
3
4
79
101
5
112