16.2. Sensible Capacity Chart

● CS-E15EKEA CU-E15EKEA
Indoor wet
bulb temp.
TC
17.0°C
4.36
19.0°C
19.5°C
4.79
22.0°C
5.22
● CS-E18EKEA CU-E18EKEA
Indoor wet
bulb temp.
TC
17.0°C
5.26
19.0°C
19.5°C
5.77
22.0°C
6.29
● CS-E21EKEA CU-E21EKEA
Indoor wet
bulb temp.
TC
17.0°C
6.25
19.0°C
19.5°C
6.86
22.0°C
7.48
TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)
30
35
SHC
IP
TC
SHC
3.31
1.25
4.08
3.17
4.40
3.46
1.28
4.48
3.33
3.59
1.30
4.88
3.45
30
35
SHC
IP
TC
SHC
3.99
1.51
4.91
3.82
5.30
4.17
1.54
5.40
4.01
4.33
1.57
5.88
4.16
30
35
SHC
IP
TC
SHC
4.74
2.02
5.84
4.54
6.30
4.96
2.06
6.41
4.77
5.14
2.10
6.99
4.95
Outdoor Temp. (°C)
40
IP
TC
SHC
1.35
3.79
3.05
1.37
1.38
4.17
3.20
1.40
4.54
3.33
Outdoor Temp. (°C)
40
IP
TC
SHC
1.63
4.57
3.67
1.65
1.66
5.02
3.86
1.69
5.47
4.01
Outdoor Temp. (°C)
40
IP
TC
SHC
2.18
5.43
4.37
2.21
2.22
5.97
4.59
2.26
6.50
4.77
83
46
IP
TC
SHC
IP
1.44
3.45
2.90
1.56
1.47
3.79
3.05
1.59
1.50
4.13
3.18
1.62
46
IP
TC
SHC
IP
1.74
4.16
3.49
1.88
1.77
4.56
3.67
1.91
1.80
4.97
3.83
1.95
46
IP
TC
SHC
IP
2.33
4.94
4.15
2.51
2.37
5.42
4.37
2.56
2.42
5.91
4.55
2.61
Indoor 27°C/19°C