Instructions and Building Regulations
This appliance must be fitted in accordance with the following
instructions.
The Local Building Regulations.
The Building Regulations.
The Building Standards, (Scotland-consolidated) Regulations.
Local water bylaws.
British Standards- code of practice.
BS 5449, 1990, forced circulating hot water systems.
BS 7671, IEE wiring regulations.
BS 4814, 1990, Specification for expansion vessels (sealed sys-
tems only)
C.O.S.H.H.
Materials used in the manufacture of this appliance are non-haz-
ardous and no special precautions are required when fitting or
servicing this appliance.
PREPARATION
1. Load Check
A load check should be taken into consideration when installing
high output boilers.
2. Boiler location
The boiler must be fitted on a wall that will provide an adequate
fixing, and should be fitted in a location that the boiler and pipe-
work are not subject to frost and damp conditions.
3. Central heating
Detailed recommendations are given in BS 5449, BS 6700 and
CP 342, Part 2.
Pipes forming part of the useful heating surface should be in-
sulated to prevent any potential heat loss or frost damage.
(BS 6700:1997).
Drain valves should be fitted at the lowest point of the system
pipe work in an accessible position.
Drain valves should be in accordance with BS 2879 and copper
tube to BS 2871. Part 1 is recommended.
LOCATION
The boiler can be installed in almost any location within a do-
mestic or commercial property, however consideration should be
given to future maintenance. Never leave the boiler switched off
if there is danger of having temperatures below 0°C in the room
where it is located.
GB-016C_f.493
PREPARATION
MOUNTING THE BOILER
Mount the boiler onto a flat wall surface that will be capable of
taking the boilers full weight. Use the mounting template provid-
ed with the boiler, mark and drill the fixing holes taking into con-
sideration you leave the minimum clearances required around
the fusion boilers.
We recommend that a minimum clearance of 450 mm should be
allocated for the removal of the front cover and adequate access
to the boiler plumbing and the internal electrical connections. A
50 mm allowance should be made at either side of the boiler to
allow free flow air into the boiler case and allow access to screws
on the boiler case (150 mm for Slimline model).
THE BOILER MUST BE INSTALLED IN THE UPRIGHT POSITION,
FAILURE TO DO SO WILL INVALIDATE THE WARRANTY.
3
Need help?
Do you have a question about the Fusion and is the answer not in the manual?
Questions and answers