Forced Operation Mode - Daikin FVXS25FV1B Service Manual

Inverter pair floor standing type
Hide thumbs Also See for FVXS25FV1B:
Table of Contents

Advertisement

SiBE06-708
3.13

Forced Operation Mode

Outline
Forced operating mode includes only forced cooling.
Detail
Forced Cooling
Forced operation
allowing conditions
Starting/adjustment
1) Command
frequency
2) Electronic
expansion valve
opening
3) Outdoor unit
adjustment
4) Indoor unit
adjustment
End
Others
Function and Control
Item
1) The outdoor unit is not abnormal and not in
the 3-minute stand-by mode.
2) The operating mode of the outdoor unit is
the stop mode.
3) The forced operation is ON.
The forced operation is allowed when the
above "and" conditions are met.
If the forced operation switch is pressed as
the above conditions are met.
25/35 class : 68Hz
50 class : 66Hz
It depends on the capacity of the operating
indoor unit.
Compressor is in operation
The command of forced operation is
transmitted to the indoor unit.
1) When the forced operation switch is
pressed again.
2) The operation is to end automatically after
15 min.
The protect functions are prior to all others in
the forced operation.
Forced Cooling
Control Specification
47