Forced Operation Mode - Daikin FTXD60JV1B User Manual

Ftxd-j series, flx-j series, rxd-j series inverter pair
Hide thumbs Also See for FTXD60JV1B:
Table of Contents

Advertisement

SiBE04-101.book Page 23 Monday, October 15, 2001 3:08 PM
SiBE04-101
1.5

Forced Operation Mode

1.5.1
J type
Operation by the
Operation Buttons
Provided at the Unit
or the Remote
Conditions
Controller
Starting
procedure,
operating
condition
Reset
A way to enter the test operation mode by a remote controller.
1. Set on the desirous mode and push ON/OFF button. (operation ON)
2. Press the center of the temperature setting button, and the "Mode" button at the same time. (then a left
3. Moreover, push "MODE" button twice. (If the liquid crystal display becomes "
Operation by the
Switch on the PCB
of the Outdoor Unit
Conditions
Starting
procedure,
operating
condition
Reset
Main Function
Item
Forced cooling
not in the 3-minute stand-by mode
normal operation mode
outdoor unit off
no malfunction in the outdoor unit
forced mode: cooling mode.
1. Keep pushing the operation switch of the
indoor unit for 5 to 10 seconds.
2. Change the remote controller setting to a
cooling test operation.
( Regarding a way to enter the test
operation, refer to the note in a margin
below)
Possible to enter the forced cooling mode by
either way of 1. or 2..
Fix operation frequency to A Hz.
Operation-on timer :15 min.
Indoor unit's fan : H tap.
Swing flap: the latest set position.
1. Push the operation switch of the indoor unit
in an usual way.
2. Push the stop button on a remote controller.
3. Operation-on timer : 15 min. overtime.
figure of the liquid crystal temperature's display number starts to blink.)
mode will startup under the mode displayed in a liquid crystal. )
Item
Forced cooling
not in the 3-minute stand-by mode
normal operation mode
outdoor unit off
no malfunction in the outdoor unit
forced mode: cooling mode.
1. Press the forced operation switch on the
outdoor PCB for not longer than 5 seconds
Fix operation frequency to A Hz.
Operation-on timer : 60 min.
Indoor unit's fan : H tap.
Swing flap: the latest set position.
1. Push the operation switch of the indoor unit
again.
2. Operation-on timer : 60 min. overtime.
3. Reset the forced cooling operation mode by
either the procedure 1 or the procedure 2.
Class
A
B
50
56
62
60
48
70
71
48
66
General Functions
Forced heating
not in the 3-minute stand-by mode
normal operation mode
outdoor unit off
no malfunction in the outdoor unit
forced mode: heating mode.
With a change of the remote controller setting
to a heating test operation, the unit enters the
forced heating mode.
(Regarding a way to enter the test operation
mode, refer to the note in a margin below)
Fix operation frequency to B Hz.
Operation-on timer :15 min.
Indoor unit's fan : H tap.
Swing flap: the latest set position.
1. Push the operation switch of the indoor unit
in an usual way.
2. Push the stop button on a remote controller.
3. Operation-on timer : 15 min. overtime.
", the test operation
23