Forced Operation Mode; Additional Function - Daikin FTXS09DVJU Service Manual

Inverter pair wall mounted type
Hide thumbs Also See for FTXS09DVJU:
Table of Contents

Advertisement

Control Specification (09/12 Class)
Detail
I Judgment by power consumption
When an output frequency is exceeds 55 Hz and the input current is less than specified value, the
adjustment is made for insufficient gas.
II Judgment by discharge pipe temperature
When discharge pipe temperature is ∆ 36°F higher than target value and the electronic expansion
value opening is 450 pulses (max.), the adjustment is made for insufficient gas.
III Judgment by the difference of temperature
When the difference of the temperature is smaller than
Cooling
Heating

3.13 Forced Operation Mode

Outline
Forced operating mode includes only forced cooling.
Detail
Forced Cooling
Forced operation
allowing conditions
Starting/adjustment
1) Command
frequency
2) Electronic
expansion valve
opening
3) Outdoor unit
adjustment
4) Indoor unit
adjustment
End
Others

3.14 Additional Function

3.14.1
Powerful Operation Mode
Compressor operating frequency is increased to PI Max. (Max. Hz of operating room) and outdoor
unit airflow rate is increased.
3.14.2 Voltage Detection Function
Power supply voltage is detected each time equipment operation starts.
46
room temperature – indoor heat exchanger temperature
outdoor heat exchanger temperature – outdoor temperature
indoor heat exchanger temperature – room temperature
outdoor temperature – outdoor heat exchanger temperature
Item
Forced Cooling
1) The outdoor unit is not abnormal
and not in the 3-minute stand-by
mode.
2) The operating mode of the outdoor
unit is the stop mode.
3) The forced operation is ON.
The forced operation is allowed when
the above "and" conditions are met.
If the forced operation switch is
pressed as the above conditions are
met.
68 Hz
It depends on the capacity of the
indoor unit.
Compressor is in operation
The command of forced operation is
transmitted to the indoor unit.
1) When the forced operation switch is
pressed again.
2) The operation is to end
automatically after 15 min.
The protect functions are prior to all
others in the forced operation.
, it is regarded as insufficient gas.
7.2°F
7.2°F
7.2°F
5.4°F
Function and Control
SiUS04-702