USERS MANUAL FOR MOBILE APPLICATIONS WHISPER 16 ULTRA -1500 RPM- Mobile diesel generating set 230V-50 Hz Digital Diesel Control MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel.: +31-20-3422100 V1. July 2004 Fax: +31-20-6971006 www.mastervolt.com...
INTRODUCTION 1 INTRODUCTION GENERAL GUARANTEE The Whisper 16 ULTRA Mobile Diesel Generating set is Mastervolt guarantees that this generating set has been manufactured and marketed by Mastervolt. built according to good workmanship, according to the It is important to read this manual before installing and specifications in this manual and according to European operating the generating set.
Mastervolt does not accept liabi- WEIGHT 420 kg lity for damage due to use of the generator, possible errors in the manuals and the results thereof. Fig. 1: Nameplate. EN / WHISPER 16 ULTRA Mobile / July 2004...
Realise hat people are not used to have Warning signs indicate parts which could 230V available on a vehicle. Put warning be live. signs on wall sockets and on junction July 2004 / WHISPER 16 ULTRA Mobile / EN...
2.1.5 Operation sources of ignition around batteries. External moving parts like fans and V-belts are covered by the canopy and therefore the Whisper 16 ULTRA is • Keep a fire extinguisher on hand. very safe, when the canopy is closed •...
After removing the generating set from long term storage perform an insulation check. (Refer to the alternator maintenance paragraph for procedures) • While the battery is stored it should be recharge every 12 weeks. July 2004 / WHISPER 16 ULTRA Mobile / EN...
The engine is water cooled and the cooling liquid is cooled by a radiator.The engine has been specially adapted for the Mastervolt application and is very different from the standard engine as supplied for industrial applications! 2.5.3 Digital Diesel Control system The standard electrical engine control system is 12 Volt negative earth, non earth return is available as optional.
(+15 m cable): fuel filter, fuel lift pump, user and installation manuals Optional installation kits, mobile (vehicle) version, non earth return, (ungrounded), spare part kits, PTO to drive hydraulic pump July 2004 / WHISPER 16 ULTRA Mobile / EN...
1,5 mm2 DCC > LCP red/green 1,5 mm2 DCC > generator AC output brown 1 mm2 DCC > generator AC output blue 1 mm2 DDC=Digital Diesel Control Unit LCP=Local Control Panel EN / WHISPER 16 ULTRA Mobile / July 2004...
INFORMATION 2.5.15 Lay out control Wiring 230V AC Radiator fan PUMP REGULATOR START/STOP WHITE (PULL) BLACK (COMM.) RED (HOLD) Fig. 7: Lay out control PCB. July 2004 / WHISPER 16 ULTRA Mobile / EN...
ROTOR BROWN BLACK (4) YELLOW/GREEN RED (3) BLUE MAIN WINDING DCC/AC-1 BLACK (4) YELLOW/GREEN EARTH AND NEUTRAL CONNECTED CURRENT TRANSFORMER BLACK (11) (11) 230V 50Hz DCC/ct-1 BROWN YELLOW/GREEN BLUE DCC/AC-1 YELLOW/GREEN EN / WHISPER 16 ULTRA Mobile / July 2004...
In operation checks: Source Selector switch to "OFF" or switch off all de- 1 Check for abnormal noise or vibration vices. 2 Check the voltage 5 Switch on the battery switch. EN / WHISPER 16 ULTRA Mobile / July 2004...
Page 18
Please note this when switching on your electrical devices! Nevertheless, the Whisper is designed so as not to overheat, even under extreme conditions. July 2004 / WHISPER 16 ULTRA Mobile / EN...
Fig. 12. down to prime the system. Retighten the bleed screw when no further air bubbles are expelled. Retighten the cap when ready. EN / WHISPER 16 ULTRA Mobile / July 2004...
1 Max. oil level; help of two screwdrivers. Install the new impeller 2 Min. oil level. and add some grease. Turn the blades in the direction of rotation of the pump. Fig. 15. July 2004 / WHISPER 16 ULTRA Mobile / EN...
(leading power factor). advice.(MASTERVOLT customers service). • Defective voltageregulator Replace voltage regulator PROBLEM CAUSE SOLUTION Generator voltage fluctuates. • Disturbances on the electrical system/ Check if electrical load is fluctuating. user side. July 2004 / WHISPER 16 ULTRA Mobile / EN...
11V, then the battery has been discharged too deep. • Starter broken. Repair the starter motor. • To thick engine lubricating oil. Change oil for a lower viscosity. EN / WHISPER 16 ULTRA Mobile / July 2004...
Page 24
Check the compression. Overfull oil sump or worn cylinder bore, stuck broken or worn rings. • Black smoke - Check the fuel . incomplete combustion caused by: Check for overload. July 2004 / WHISPER 16 ULTRA Mobile / EN...
Page 25
Have the compression measured. damaged piston rings. Clean or replace the rings. • Wear out of cylinders. Have the compression measured and have the engine overhauled. Over-temperature • Overload. Take away the overload. EN / WHISPER 16 ULTRA Mobile / July 2004...
Moreover the generating set is fixed motor by 2 fail safes that prevents the generating set of getting loose when the rubber mountings would break EN / WHISPER 16 ULTRA Mobile / July 2004...
Page 28
All cables and wiring has to be check very carefully for leakages before putting it taken loose first. back in its enclosure. 6 The rotor can be taken off by removing the bold which July 2004 / WHISPER 16 ULTRA Mobile / EN...
TROUBLE SHOOTING MAINTENANCE LOG first service after 50 hours: hour counter: remarks: next service (every 150 hours) hour counter: remarks: EN / WHISPER 16 ULTRA Mobile / July 2004...