Optex HX-40 Installation Instructions Manual page 14

High mount outdoor detector
Table of Contents

Advertisement

-AUX INPUT
By connecting a satellite unit (another warning sensor), you can extend the detection area
and correct false alarms. As a satellite unit, you can use any general no-voltage contact
output (NC) warning sensor, including the following.
<Infrared (AIR) sensors, thermal line (PIR) sensors, universal magnet switches, etc.>
POSITION
AND
OR
-TROUBLE OUTPUT
Trouble output is used for anti-masking signal.
When an object is placed close to the lens surface, for a period of more than 180 sec., the IR
Anti-Masking circuit is activated and generates a trouble signal.
POSITION
OFF
ON
-MICROWAVE IMMUNITY
POSITION
IMMUNITY
STD
IMMUNITY
AND
When both the main unit and the satellite detect someone, the
(Factory
alarm is output.
default)
Set to this when not connecting a satellite unit.
When either the main unit or the satellite detects someone,
OR
the alarm is output.
Notes>>
The alarm does not output unless both the main unit and the satellite
detect someone within 60 sec.
If the OR mode is selected without a satellite unit connected, the alarm
is generated continuously.
ON
Anti-masking signal is output from TROUBLE OUTPUT
(Factory
terminal.
default)
Anti-masking signal is output from both TROUBLE and
OFF
ALARM OUTPUT terminal.
Note>>
Use this when not wiring a detected trouble input terminal on the control
panel.
STD
(Factory
MICRO WAVE IMMUNITY logic is not activated.
default)
MICRO WAVE IMMUNITY logic is activated. Use this
under harsh environment (e.g. vegetation sway).
FUNCTION
FUNCTION
FUNCTION
- 14 -
3
DIP switch
4
DIP switch
5
DIP switch
HX-40
HX-40AM
HX-40DAM
HX-40
HX-40AM
HX-40DAM
HX-40
HX-40AM
HX-40DAM