Maintenance; Adjustments; Pilot Burner Adjustment; Venturi Adjustment - Napoleon BGNV42N Installation And Operation Instructions Manual

Millivolt system vented natural and propane gas fireplace
Table of Contents

Advertisement

Turn off the gas and electrical power before servicing
the fireplace.
CAUTION: Label all wires prior to disconnection when serv-
icing controls. Wiring errors can cause improper and dan-
gerous operation. Verify proper operation after servicing.
This fireplace and its venting system should be inspected
before use and at least annually by a qualified service per-
son. The fireplace area must be kept clear and free of com-
bustible materials, gasoline or other flammable vapours
and liquids. The flow of combustion and ventilation air must
not be obstructed.
1. In order to properly clean the burner and pilot assembly,
remove the logs to expose both assemblies.
2. Keep the control compartment, logs, burner
opening and the area surrounding the logs clean by vacu-
uming or brushing, at least once a year.

PILOT BURNER ADJUSTMENT

Adjust the pilot screw to provide properly sized flame. Turn
in a clockwise direction to reduce the gas flow.
PILOT SCREW
FIGURE 28

VENTURI ADJUSTMENT

MODEL BGNV42
NG
LP
Closing the air shutter will cause a more yellow flame, but
can lead to carboning. Opening the air shutter will cause a
more blue flame, but can cause flame lifting from the burner
ports. The flame may not appear yellow immediately; al-
low 15 to 30 minutes for the final flame colour to be estab-
lished.

MAINTENANCE

,
air shutter

ADJUSTMENTS

FIGURE 29
FIGURE 30
1/8"
5/16"
3. Check to see that all burner ports are burning. Clean out
any of the ports which may not be burning or are not burn-
ing properly.
4. Check to see that the pilot flame is large enough to
engulf the thermocouple and thermopile and reaches to-
ward the burner with the third jet.
5. Replace the cleaned logs.
6. Check to see that the main burner ignites completely on
all openings when the gas knob for the burner is turned
on. A 5 to 10 second total light-up period is satisfactory. If
ignition takes longer, consult your Napoleon dealer / dis-
tributor.
7. Check that the gasketing on the sides, top and bottom of
the door is not broken or missing. Replace if necessary.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A
QUALIFIED GAS INSTALLER!
FIGURE 30
To access the air shutter, remove the two screws that se-
cure the cover to the air housing, taking care not to dam-
age the gasket.
FIGURE 31 (not exactly as shown)
13
VENTURI
COVER
W415-0377 / 03.04.03

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bgnv42p

Table of Contents