Connecting the connection cord

Always remember to connect the refrigerant pipes before performing the electric connections.
When disconnecting the system, always disconnect the electric cables before disconnecting the refrigerant pipes.
Always remember to connect the air conditioner to the grounding system before performing
the electric connections.
14
E-
CH」ェ」ェ」ェEAV_IM_E_26918.indd
14
 A lways remember to connect the air conditioner to the grounding system before performing
the electric connections.
CAUTION
The indoor unit is powered by the outdoor unit by means of a H07 RN-F
connection cable (or a more power model), with insulation in synthetic rubber
and jacket in polychloroprene(neoprene), in accordance with the requirements
of standard EN 60335-2-40.
1
Remove the screw on the electrical component box and remove the cover plate.
2
Route the connection cord through the side of the indoor unit and connect
the cable to terminals; refer to the figure below.
3
Route the other end of the cable to the outdoor unit through the ceiling &
the hole on the wall.
4
Reassemble the electrical component box cover, carefully tightening the screw.

Wiring diagram

Outdoor unit
Power Supply
220-240V~/50Hz
For connection cord, use the grade H07RN-F or H05RN-F materials.
S crews on terminal block must not be unscrewed with the torque less than 12 kgf•cm.

Indoor unit
Communication
Between Indoor and Outdoor Connection Cord Specifications
Power Supply (Single Phase)
Max/Min(V) Connection Wire
10%
1.25mm
±
Power
Earth Cable Communication Cable
2
0.75~1.25mm
2
Ø 1.6mm,1 wire
2 wires
2007-05-10
ソタネト 3:51:56