Heat-N-Glo 6000TRXI Installer's Manual page 13

Table of Contents

Advertisement

Flex Vent
The flex vent must be supported with the spacing be-
tween support intervals not exceeding 4 feet, with no
more than ½ inch sag between supports.
A support is required at each change in venting direc-
tion, and in any location where it is necessary to main-
tain the necessary clearance to combustibles. A simple
"up and out" installation (Figure 6) requires only
enough support to maintain the necessary clearance
to combustibles. However, the vent attachment point
and the firestop location are considered to be supports.
3" CLEARANCE
FLEX-VENT
Figure 6.
STRAIGHT UP
VERTICAL VENTING
V (FT.)
40' MAX. (12.4 M)
NOTE: On vertical venting
configurations you may
want to install the vertical
baffle (385-128). See flue
restrictor installation in-
structions.
Figure 7.
Straight Up Vertical Venting
Flue Restrictor Instructions
1. Remove Exhaust Shield using a 1/4" nut driver by
TERMINATION
CAP
1"
CLEARANCE
RESTRICTOR
Figure 8
2. Break the Flue Restrictor into two pieces. Do this
Figure 9.
13
removing the four screws securing it in place (see
Figure 8).
EXHAUST
SHIELD
FLUE
by bending the part back and forth until it breaks
(see Figure 9).
BREAK
HERE
Flue Restrictor

Advertisement

Table of Contents
loading

Table of Contents