Burner Adjustment Tables - Riello F3 Installation Manual

40 series residential oil burners
Table of Contents

Advertisement

NON-RETROFIT APPLICATIONS
If this burner is being installed in a packaged unit (i.e. Burner comes with a boiler or furnace), follow the
installation and set-up instructions supplied with the heating appliance, as settings will differ from those
shown in this manual.
1
ACTUAL FIRING
RATE 5% ±
US GPH
0.50
0.60
0.75
0.80
0.95
1
ACTUAL FIRING
RATE 5% ±
US GPH
0.75
0.85
1.00
1.10
1.25
1.50
1.65
NOTE: The above set up charts are a starting point only. The burner and appliance must be properly set
up using proper combustion testing equipment.
Note: any approved oil burner nozzle type, angle and manufacturer maybe used, as long as input
is corresponding the correct BTU/hr. or US gph input rating of the appliance.
COMBUSTION CHAMBER
Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the
appropriate installation codes (e.g. CSA B139 or NFPA #31).
C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006

BURNER ADJUSTMENT TABLES

MODEL F3 BURNER SETUP CHART
2
NOZZLE
SIZE
PRESSURE
GPH
PSI
.40 x 60º/80º
160
.50 x 60º/80º
150
.60 x 60º/80º
150
.65 x 60º/80º
150
.75 x 60º/80º
160
MODEL F5 BURNER SETUP CHART
2
NOZZLE
PUMP
SIZE
PRESSURE
GPH
PSI
.60 x 60/ 80º
145
.65 x 60/ 80º
145
.85 x 60/ 80º
145
1.00 X 60/ 80°
145
1.10 x 60/ 80º
145
1.25 x 60/ 80º
145
1.35 X 60/ 80°
145
3
4
PUMP
TURBULATOR
SETTING
BAR
11.0
0.0
10.4
0.5
10.4
1.5
10.4
2.0
11.0
3.0
3
4
TURBULATOR
BAR
SETTING
10
0.0
10
0.5
10
1.0
10
2.0
10
2.5
10
3.0
10
4.0
5
AIR DAMPER
SETTING
2.3
2.7
3.4
3.6
4.3
5
AIR DAMPER
SETTING
2.25
2.5
2.75
3.0
3.5
4.25
6.0
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

F5