B) TWO LINE (LIFT SYSTEM)
Turn off the main power source to the burner and remove the air tube cover. Shines a light source on the
photocell (now visible where the air tube cover was removed), return power to the burner and activate the
burner. With the light source in place, the burner will operate in prepurge only. When the pump is sufficiently
purged, the hydraulic air shutter will open. Once the burner is purged, turn off the power source and replace the
air tube cover. Return power to the burner. The burner is now ready to operate.
ATTENTION: It is important that the fuel line be completely sealed and free from air leaks or any internal
blockages.
WARNING! WHEN THE BYPASS PLUG IS INSTALLED, A TWO-PIPE SYSTEM MUST BE USED OR
FAILURE OF THE PUMP SHAFT WILL OCCUR.
A) The hydraulic AIR SHUTTER (1) is operated by the HYDRAULIC JACK (6), assuring complete opening
of the combustion air intake. Regulation of the combustion airflow is made by adjustment of the manual
AIR ADJUSTMENT PLATE (4) after loosening the FIXING SCREWS (3 & 5). The initial setting of the air
adjustment plate should be made according to Column 5 in the Burner Setup Charts on page 15.
B) The proper number on the manual AIR ADJUSTMENT
PLATE (4) should line up with the SETTING
INDICATOR (2) on the fan housing cover. Once set, the
air adjustment plate should be secured in place by
tightening SCREW 3 and 5. Manually open and release
the hydraulic shutter to ensure it has free movement.
C) The final position of the air adjustment plate will
vary on each installation. Use instruments to establish
the proper setting for maximum CO
zero.
NOTE: Variations in flue gas, smoke, CO
put in place. Therefore, the burner cover must be in place when making final combustion instrument readings,
to ensure proper test results.
C6501010 STANDARD F3-5 MANUAL Rev. 3-2 10/12/2006

SETTING THE AIR ADJUSTMENT PLATE

and a smoke reading of
2
and temperature readings may be experienced when burner cover is
2
1
2
3
14
6
5
4