13. Select switch on
1. Setting remote controller
remote controller
• Remove the cover, and insert the batteries.
• Push the "CHECK" point and "MODE" button at
B
START/STOP
FAN
MODE
SWING
ECO
TIMER
FIX
ON
OFF
FILTER
2. Setting the unit
• Remove the cover of the electric parts box by taking off the mounting screws (3 positions)
• There are the selector switches (SW02) on the P.C. board of the electric parts box.
• Check whether the changed remote controller can operate the indoor unit or not.
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Operation flow and applicable data, etc.
once for changing remote controller setting from "A"
to "B". (Priority is given to "A" setting.)
When it is "B", "B" is displayed.
When it is "A" , none is displayed.
AM
:
PRESET
Push the "CHECK" point and
"MODE" button at once.
AUTO
Hi POWER
MEMO
SET
CLR
RESET CLOCK CHECK
and pushing the hooking section.
(The cover of the electric parts box remains hanged to the hinge.)
No.4 of the selector switches (SW02) is provided to select the switch of the remote controller.
Select ON of No.4 of the selector switches (SW02). (OFF: A setting, ON: B setting)
www.heronhill.co.uk
1. Purpose
2. Description
3. Operation
– 34 –
Description
This operation is to operate only
one indoor unit using one remote
controller.
When operating one indoor unit in
a situation where two indoor units
have been installed in the same
room or nearby rooms, this
operation prevents the remote
controller signal from being
received simultaneously by both
units, thus preventing both units
from operating.
The indoor unit on which the
remote controller selection has
been set to B receives the signal of
the remote controller also set to B.
(At the factory the remote controller
selection is set to A on all the
indoor units. There is no A setting
display.)
ON
6H
1
2 3 4
SW01
TS ADJUST
ON
ON
"B" setting
6H
SW02
1
2 3 4
"A" setting