INSTALLATION INSTRUCTIONS GB/IE GLOBAL 55 CF GLOBAL 55XT CF FITTING INTO A CONvENTIONAL CLASS 1 ChImNEy DRU VERWARMING B.V. HOLLAND 957.771.00...
CONTENTS Site: Important Foreword Instructions for installation Ventilation Chimney and Flue System Requirements Checking the Class 1 Chimney’s Performance Prior to Building the Builders Opening Builders Opening Requirements Preparing the Appliance for Installation into the Builders Opening Using a Flue Liner Fitting into a Conventional Class1 Chimney Spillage Test Figures...
INSTRUCTIONS FOR INSTALLATION Important Foreword • These installation instructions are Dear Customer, supplementary to the Installation Manual and User Manual. In this booklet you will find instruc- tions for the Installation of the appli- Gas Safety Regulations ance in a builder’s opening/fireplace (for Installation and Use) 1998.
Blocked. may be a slight loss in heat input. Ventilation Requirements The Global 55 CF and Global 55 XT The design of this fire is such that CF is a open-flued appliances. the appliance can be completely As a result, the room in which the...
INSTRUCTIONS FOR INSTALLATION - Make sure that combustible objects (Global 55XT CF) high and between and/or materials have a distance 570mm and 590mm wide. from the appliance of at least 500 mm. • The builders opening should be at least 330 mm deep. •...
INSTRUCTIONS FOR INSTALLATION marble are fixed and sealed around • Attach the appliance with the screws the builders opening. See also the through the holes in the flanges of installation manuel. the appliance. • This will help to reduce wall •...
INSTRUCTIONS FOR INSTALLATION Spillage Test Caution The spillage test is intended to check - Ensure the foam seal is sealing up the draft in the chimney. The spillage against the front face of the builders test can only be opening. performed if the appliance is fully - The appliance must be fully sealed installed.
Page 8
INSTRUCTIONS FOR INSTALLATION • Check if the pressure is according to table below: - If the pressure is the same as the minimum according table, the test is successful - If the pressure is lower than the minimum according the table there is spillage and the fire must not be used until this is rectified.
Page 9
INSTRUCTIONS FOR INSTALLATION Flat Area The builders opening The depth of the opening must be 330 minimum 570 -590 38c-2112 Fig. 1 Fitting into a Conventional Class1 Chimney...